UTC Fire & Security Americas Corporation Inc 561M-FREEZE User Manual

Page of 2
 
P/N 46-550 
• REV B • 06JUN14 
 
Learn Mode Freeze Sensor Installation 
Instructions 
Overview 
The ITI Learn Mode (LM) Freeze Sensor contains a thermal 
couple wired to a transmitter. The LM Freeze Sensor detects a 
furnace failure in a home or business. It activates a switch 
(thermal couple) when the surrounding temperature drops to 
~45°F. After the sensor is tripped, a temperature between 55°F 
and 60°F is necessary for the device to send a restore signal. 
The LM Freeze Sensor: 
• 
Contains an RF transmitter capable of transmitting over 
500 feet. 
• 
Is powered by a 3.5-Vdc lithium battery, which lasts 5-8 
years. 
• 
Sends a Trouble (Low Battery) report to the CPU. 
• 
Sends a supervisory signal to CPU every 64 minutes. 
• 
Has an operating range of 10°F to 120°F. 
• 
Contains a built-in tamper switch. Remove the sensor 
cover to trip the switch. The sensor then transmits a 
Trouble signal to the CPU. 
• 
Has a tamper switch, which cannot be disabled. 
• 
Monitors an open area of about 900 square feet (30’ x 
30’). 
Installation Considerations 
DO 
• 
Try to keep sensors within 100 feet of the CPU. The 100-
foot distance recommendation is given as a starting 
guideline. The transmitter has an open-air range of over 
500 feet, but the installation environment may affect this 
range. 
• 
Locate the sensor in an area that is likely to get cold first. 
• 
Locate the sensor on an interior wall where there is free 
movement of air. 
DO NOT 
• 
Locate the sensor in the same room as a furnace, water 
heater, or any other heat source that may stay warm after 
the furnace fails.  
• 
Locate the sensor on an outside wall or near the 
basement floor. 
• 
Place in areas with excessive metal or electrical wiring. 
These items may inhibit the sensor’s signals from reaching 
the CPU. 
• 
Place sensor in an area where it will be exposed to 
moisture. 
• 
Place the sensor in an area where the temperature will fall 
outside the sensor’s operating limits (10°F-120°F). 
Installation 
CAUTION: 
You must be free of all static electricity when 
handling transmitters. Touch a grounded metal object 
before handling the circuit board. Handle the circuit board 
by the edges and never set the circuit board on any 
metallic surface. 
1.  Press on the cover end to disengage the top of the cover 
from the slot in the sensor base, and then remove the 
transmitter cover. 
2.  Remove the circuit board from the transmitter base by 
pushing back on the base release tab. See Figure 1.