Phones Menu (1st Tier)
The phone menu lets you set up central station reporting for 
the system.
Number 1 and 2
 (Phones—Phone 1 and Phone 2)
3rd Tier
(Default = none, Parameters = 24 digits; 0-9, *, #) This setting 
is used for programming the central station receiver phone 
number. Phone numbers can be 1 to 24 digits long, including 
pauses or * and # characters. 
To enter pauses, press the silent key. A pause is displayed as P.
To enter *, press and hold the 7 key until * appears. A star (*) 
is displayed as *.
To enter #, press and hold the 9 key until + appears. A pound 
(#) is displayed as +.
Note 
The phone numbers are not accessible if a Dealer Code is 
programmed and the Installer Code is used to enter 
installer programming mode. To access these numbers 
when a Dealer Code is programmed, you must enter 
installer programming mode using the Dealer Code. 
Note 
Call-waiting services should be disabled to prevent inter-
rupting panel communication to the central monitoring sta-
tion. To program a dialing prefix that disables call-waiting, 
see Pre-Dial String on page 8.
To program number 1/2:
Enter 1-24 digit number and press 
#
FMT - CID
 (Phones—Phone 1 and Phone 2)
3rd Tier
(Default = CID) This setting determines whether the panel 
uses the SIA (off) or CID (on) reporting format for central 
station communication. 
To select reporting format under phone 1/2:
‰ Press # to select on or off. 
High Lvl
 (Phones—Phone 1 and Phone 2)
3rd Tier
(Default = Phone 1: on, Phone 2: off) When High Level 
Reporting is on, the following conditions report to the central 
station:
Fire, Police, Emergency, and Duress alarms
Phone Test
Receiver Trouble
Entering or Exiting Sensor Test Mode
Tamper Conditions, including Zone Tampers and System 
Tamper (40 incorrect key presses)
No Activity
Note 
For UL listed installations, High and Low-level reports must 
be set to on.
To turn high-level reports on or off under phone 1/2:
‰ Press # to turn it on or off. 
Low Lvl
 (Phones—Phone 1 and Phone 2)
3rd Tier
(Default = Phone 1: on, Phone 2: off) When this setting is on, 
the following non-alarm conditions report to the central 
station: 
Forced Arming
Hardwire Zone Trouble 
RF Supervisory 
RF Low Battery 
Phone Test
To turn low-level reports on or off under phone 1/2:
‰ Press # to turn it on or off. 
Openings
 (Phones—Phone 1 and Phone 2)
3rd Tier
(Default = off) This setting determines whether an opening 
report is sent to the central station. When turned on, the panel 
sends an opening report when the system is disarmed.
To turn opening reports on or off under phone 1/2:
‰ Press # to turn it on or off. 
Closings
 (Phones—Phone 1 and Phone 2)
3rd Tier
(Default = off) This setting determines whether a closing 
report is sent to the central station. When turned on, the panel 
sends a closing report when the system is armed.
To turn closing reports on or off under phone 1/2:
‰ Press # to turn it on or off. 
Backup
 (Phones—Phone 2)
3rd Tier
(Default = on) This setting determines whether the DTIM uses 
phone number 2 for reporting if three initial attempts on phone 
number 1 are unsuccessful. 
PHONE
 1 is backed up by 
PHONE
  2. 
The DTIM makes up to 16 attempts (8 per phone number), 
alternating between the two programmed phone numbers.
For example, if Backup is on and three failed reporting 
attempts occur using 
PHONE
  1, (panel displays 
PHONE
 1 
FAIL
), the 
DTIM switches to 
PHONE
 2 for three more reporting attempts. 
If these attempts fail, (panel displays 
PHONE
 2 
FAIL
), the DTIM 
switches back to 
PHONE
  1 for five more reporting attempts and, 
if necessary, switches back to 
PHONE
 2 for five final attempts. 
If these final attempts fail, the panel will display 
PHONE
 
FAILURE
.
To turn backup on or off:
‰ Press # to turn it on or off.