UTC Fire & Security Americas Corporation Inc 808-UFT User Manual

Page of 4
3
Preliminary 1/22/02
instructions or reference manual for complete programming 
details.
1.
Set the panel to program mode.
2.
Proceed to the LEARN SENSORS menu.
3.
Select the appropriate zone type and zone number 
assignments.
4.
Set the external switch in the alarm condition (open for 
a normally closed circuit, closed for a normally open 
circuit).
5.
Trip the sensors tamper switch by removing the sensor 
cover.
6.
Exit program mode.
7.
Place the cover back on the sensor.
Testing
The following steps describe the general guidelines for test-
ing the sensor. Refer to the specific panel installation 
instructions or reference manual and the instructions for the 
external switch for complete testing details.
1.
Set the panel to the installer zone test mode.
2.
Trip the sensor.
3.
The signal strength from the UFT will be displayed on 
all keypads. It should be 15 or higher for proper opera-
tion.
Specifications
Operating Temperature 
Range: ........................... 10° to 120° F
Compatibility: ............... Advent Commercial Fire 250 Zone 
(60-562-03)
Advent Commercial Fire 132 Zone 
(60-562-06)
Advent Commercial Burg 250 
Zone (60-562-01)
Advent Commercial Burg 132 
Zone (60-562-04)
Power Source: ............... 1 AA 3.6-volt lithium battery (not 
replaceable)
Transmit Range: ............ At least 500 feet, open air