SuperBus 2000 319.5 MHZ RF Transceiver Module Installation Instructions
Preliminary 8/5/04
¾
To mount the module on a wall:
1. Remove the panel AC power transformer and disconnect the backup battery.
2. Remove the module cover and set it aside.
3. Hold the base against the mounting surface and mark the three mounting holes. Remember to 
leave at least 10 inches
 
above the base for the antenna.
4. Drill holes and insert the appropriate anchors.
5. Secure the back-plate to the wall with included panhead screws.
Concord Panel Wiring
This section describes how to wire the transceiver module to Concord panels.
¾
To wire the transceiver module to Concord panels:
1. Disconnect the panel power transformer and backup battery.
2. Wire the module to the panel power and bus terminals as shown in Figure 3.
Figure 3. Wiring Module to Concord Panel
Power Up
Use the following procedures for powering up the system and verifying bus communication.
Note 
In order to enter panel pro-
gram mode to verify unit 
numbers, an alphanumeric 
touchpad must be con-
nected to all Concord pan-
els.
¾
To power up the panel and transceiver module:
1. Verify that all wiring at the panel, touchpad, and transceiver is correct.
2. Connect the panel backup battery and plug in the panel AC power transformer.
3. Verify that the transceiver module status LED is on.
4. If desired, enter panel program mode to verify unit number exists (see panel Installation 
Instructions for more information).
Note  
If the transceiver module LED is not on, unplug the panel AC power transformer, disconnect the backup 
battery, and see Table 3 “Troubleshooting”.
Specifications
Compatibility: ............................GE Security Concord panels. GE Security 319.5 MHz wireless sensors and 
touchpads
Power Required: ........................12 VDC nominal 200 mA maximum draw (from panel)
Storage Temperature:.................-30° to 140°F (-34° to 60°C)
Operating Temperature: ............. 32° to 140°F (0° to 60°C)
Maximum Humidity: .................90% relative humidity, noncondensing
Wireless Signal Range:.............. 1,500 feet nominal, 1,500 feet typical open air (may vary with application)
Dimensions:  .............................. 4.125” x 5.25” x 1.0” (L x W x H), excluding antenna
To prevent damaging the panel or module, remove the panel AC power transformer 
and disconnect the backup battery before installation.
Caution
!
You must be free of static electricity before handling circuit boards. Wear a ground-
ing strap or touch a bare metal surface to discharge static electricity.
Static
6
3
4
5
PANEL 
TERMINAL STRIP
+12
VDC
BUS
A
BUS
B
GND
SUPERBUS 2000
RF  TRANSCEIVER MODULE
 
TERMINAL STRIP
4
1
2
3
+12
VDC
BUS
A
BUS
B
GND