UTC Fire & Security Americas Corporation Inc 910C-SIMON User Manual
Chapter 4
Programming
47
Reporting
Table 18 and Table 19 on page 49 provide report option details.
Table 18. Reporting options
Function
Default
Description
Opening reports Off
Determines whether the panel sends opening reports to a central station whenever the
system is disarmed (on), or not (off). User number will be reported as zone number.
Keyfobs learned into zone 1 to 40 will report as zone they are learned into.
Dealer code = 44
Installer code = 45
Master code = 46
User code 1 = 47
User code 2 = 48
User code 3 = 49
User code 4 = 50
User code 5 = 51
User code 6 = 52
User code 7 = 53
User code 8 = 54
Duress code = 55
system is disarmed (on), or not (off). User number will be reported as zone number.
Keyfobs learned into zone 1 to 40 will report as zone they are learned into.
Dealer code = 44
Installer code = 45
Master code = 46
User code 1 = 47
User code 2 = 48
User code 3 = 49
User code 4 = 50
User code 5 = 51
User code 6 = 52
User code 7 = 53
User code 8 = 54
Duress code = 55
Closing reports
Off
Determines whether the panel sends closing reports to a central station whenever the
system is armed (on), or not (off). User number will be reported as zone number. Keyfobs
learned into zones 1 through 40 will report as the zone they are learned into.
Dealer code = 44
Installer code = 45
Master code = 46
User code 1 = 47
User code 2 = 48
User code 3 = 49
User code 4 = 50
User code 5 = 51
User code 6 = 52
User code 7 = 53
User code 8 = 54
Duress code = 55
system is armed (on), or not (off). User number will be reported as zone number. Keyfobs
learned into zones 1 through 40 will report as the zone they are learned into.
Dealer code = 44
Installer code = 45
Master code = 46
User code 1 = 47
User code 2 = 48
User code 3 = 49
User code 4 = 50
User code 5 = 51
User code 6 = 52
User code 7 = 53
User code 8 = 54
Duress code = 55
Force armed
Off
Determines whether the panel sends a force armed report to a central station if the user
bypasses protesting sensors (indirect bypass) when arming the system (on) or not (off).
bypasses protesting sensors (indirect bypass) when arming the system (on) or not (off).
AC power failure Off
Determines whether or not the panel sends AC power failure reports to a central station
after the programmed time expires. The time can be set from 005-254 minutes.
after the programmed time expires. The time can be set from 005-254 minutes.
• When the panel is without AC power for 30 seconds, the panel LEDs turn off.
• When the panel is without AC power for the programmed time, an AC power failure
• When the panel is without AC power for the programmed time, an AC power failure
is reported.
• The panel reports an AC power restoral when AC power returns to the panel.