Panduit 1167 User Manual

Page of 40
SynapSense
®
 2.4GHz Industrial Gateway 
Hardware Installation Manual 
 
12 
 
 
 
Introduction 
 
This chapter provides the scope, overview and kit components for installing and 
configuring a SyapSense
®
 2.4GHz Industrial Gateway. 
 
Scope 
 
This document provides guidelines and instructions for installing and configuring the 
Industrial Gateway. 
 
 
NOTE: Installation of SynapSoft™ software (such as MapSense™) occurs prior to 
hardware installation. This installation order prevents redundancy of hardware 
verification activities (for example, sensor-to-software communication validation).  
See Document References section for document list. 
 
 
Overview 
 
The Model 1167, SynapSense
® 
 2.4GHz Industrial Gateway, is a wireless, 2.4GHz, 
802.15.4  to wired Ethernet gateway that collects data from any of the SynapSense 
wireless sensors or meter hardware deployed throughout the plant or data center. For 
example, using SynapSense
®
 ThermaNode™ environmental sensors, data can be 
acquired across the entire active area of the plant or data center. The Model 1167 
Industrial Gateway is powered by either a dedicated 24VDC nominal power supply (10-
30Vdcmax) or an IEEE 802.3af Power over Ethernet (POE) compatible network source. 
Both power supply connections are designed to provide the user with a worry free 
installation; this allows the power supply wiring to be connected to the Model 1167 
Industrial Gateway without worrying about the polarity of the power supply’s wiring. If both 
supplies are connected, the Industrial Gateway will operate with redundant power 
supplies, allowing one of the power supplies to fail without any noticeable data 
interruption to the downstream server. 
   
Figure 1 
shows a block diagram of a typical installation with wireless data from 
various sensors arriving at the Industrial Gateway(s), and the Ethernet data path 
from the Industrial Gateway(s) to the server via wired IEEE 802.3 Ethernet.