Panduit 1167 User Manual

Page of 40
SynapSense
® 
2.4GHz Industrial Gateway 
Installation Manual 
 
17 
 
 
Installation Procedures 
 
This chapter describes general guidelines and specific procedures for configuring 
and installing the Industrial Gateway. 
 
 
General Installation Guidelines 
 
 
•  Be consistent. All installations should match in appearance where possible 
(including centering, location, method for securing extra wire, etc.) 
•  Be neat. Ensure installation is straight and vertical or horizontal as much as 
possible. 
•  Install Industrial Gateway on flat smooth surfaces such as the tops of server 
cabinets. 
•  Use adhesive cable clips to keep cable and Power wires neat and contained. 
•  Each installation location should have the desired Ethernet port within 100m of 
the Industrial Gateway. 
•  Industrial Gateway installations should not be in areas where concrete walls, 
support pillars, large cable bundles, air ducting, or other metal enclosures that 
can block the wireless signal transmission to the sensors. If a wireless line of 
sight obstruction is immovable, the external dipole Antenna of the Industrial 
Gateway can be extended by up to 50 ft. by using coaxial extension cable rated 
for 2.5GHz frequencies or higher.  The recommended antenna extension cable 
for the Industrial Gateway is rigid CNT-240 or equivalent which has less RF 
loss at 2.4GHz than standard flexible coaxial cables. The extension cable must 
be environmentally rated for the specific installation area. 
•  Keep installation area clean during and after installation. 
 
The following sections provide general information and specific installation instructions 
for installing the Industrial Gateway. The diagram below shows the typical installation 
process flow.