The final section shows which alarms are active in the system. If no alarms are
detected then the text will show ‘OK’. There are 51 different alarm conditions which
can be displayed here. If the alarms are not set up (have no check boxes checked in
the alarm matrix) then the alarm will be disabled and will not show up in this area.
13.2 Rectifier Status
The Rectifier Status page presents detailed information about an individual rectifier
module. Two types of data are included; ‘live’ status information and ‘static’ inventory
information. In addition the controller returns the I²C address as confirmation that
the unit has responded.
Figure 12 - Rectifier Status WEB Applet (typical)
In order to obtain status information about a particular rectifier module select it
by using the serial number drop down at the top right where a list of all installed
rectifiers can be seen.
‘Live’ data includes the following and is presented in the form of 8 colored indicator
blocks to the left. A green block indicates a ‘good’ condition and a red block indicates
a ‘bad’ condition. In addition the unit’s internal temperature is presented on the right.
Note that Sigma Series rectifiers include a single fan only and that two of the status
indicator blocks will always be grayed out.