X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
 
The final section shows which alarms are active in the system.  If no alarms are 
detected then the text will show ‘OK’.  There are 51 different alarm conditions which 
can be displayed here.  If the alarms are not set up (have no check boxes checked in 
the alarm matrix) then the alarm will be disabled and will not show up in this area.
13.2  Rectifier Status
The Rectifier Status page presents detailed information about an individual rectifier 
module.  Two types of data are included; ‘live’ status information and ‘static’ inventory 
information.  In addition the controller returns the I²C address as confirmation that 
the unit has responded.
 
Figure 12 - Rectifier Status WEB Applet (typical)
In order to obtain status information about a particular rectifier module select it 
by using the serial number drop down at the top right where a list of all installed 
rectifiers can be seen.
‘Live’ data includes the following and is presented in the form of 8 colored indicator 
blocks to the left.  A green block indicates a ‘good’ condition and a red block indicates 
a ‘bad’ condition.  In addition the unit’s internal temperature is presented on the right.
Note that Sigma Series rectifiers include a single fan only and that two of the status 
indicator blocks will always be grayed out.