Unique Broadband Systems Ltd. DRU2KW User Manual
Page 29
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
‘Inventory’ data, presented on the right below the temperature measurement includes,
among other items, rectifier model number Serial Number and Revision Number.
13.2.1 Rectifier Inhibit (Shutdown)
The X75 includes a facility that enables the user to manually inhibit or
shutdown individual rectifiers. This may be desirable when a particular
rectifier is to be removed from the system for maintenance, although all
UNIPOWER rectifiers are Hot-Swap, or for some other reason.
To inhibit a rectifier first select it as previously described and then click on
INHIBIT. A password entry box will appear where it will be necessary to
enter either the administrator (default 9876) or the user password (default
1234).
To restart a rectifier that has been inhibited select the desired rectifier and
click on RUN and enter the password as directed.
Note that any rectifiers which have been inhibited will remain in this state
until they are either restarted using the above method or the AC power is
recycled.