X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Enable Scheduled Equalization checkbox.  Some batteries require equalization 
to be applied periodically.  Check this check box to enable this feature.  Further 
parameters must be set up to use this feature correctly.
Equalization Voltage.  The voltage to which the rectifiers will be raised to achieve 
the boost/equalize function.
Equalize for.  The equalization will operate for this length of time (in minutes) 
before dropping back to the float voltage (with temperature compensation if enabled).
Number of days between equalizations.  Set this parameter to determine how often 
the equalization function will operate (in days).
Time of day for equalization.  Use the spinners to set the time of day that the 
equalization function will begin.  This is usually chosen to be an off peak time.
Stop Equalization if charge current exceeds.  The equalization or boost will be 
terminated if the battery charge current exceeds this value.  Equalization will also 
stop if the battery temperature exceeds 38°C. (Fixed threshold).
Buttons Start Equalization and Stop Equalization may be used to manually start and 
stop the equalization process.  Once started, the equalization will stop automatically if 
any of the above parameters are exceeded (equalization time, equalization maximum 
current, battery temperature above 38°C).
Note that it is necessary to enter the administrator  or user password to manual start 
or stop equalization.
13.3.5 - LVD
Figure 17 - Installation WEB Applet - lvd tab (typical)