X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Calculated Maximum Float Voltage.  This is the maximum voltage that the system 
can adjust to given the temperature compensation slope, nominal float voltage and 
temperature compensation temperature limits.
Calculated Minimum Float Voltage.  This is the minimum voltage that the system 
can adjust to given the temperature compensation slope, nominal float voltage and 
temperature compensation temperature limits.
Enable Temperature Compensation check box.  If this box is checked, the system 
will apply temperature compensation to the float voltage.  If not, the system will 
always output the nominal float voltage unless equalization, testing or charge current 
limit is active.
13.3.3 - Battery
Figure 15 - Installation WEB Applet - battery tab (typical)
The Battery tab allows data about the batteries attached to the system to be entered 
as below:
Number of cells.  This is used in the calculation of temperature compensation.  It 
is the total number of cells in one battery string (e.g. normally 24 cells for a 48V 
system with 2V per cell lead acid cells)
System voltage.  Choose from 12, 24 or 48V.
Number of Strings.  Number of strings of batteries attached to the system.  Note 
that X75 only allows connection of a single battery string and that this setting should 
therefore be 1 or 0 (if no batteries are connected).