X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
13.8  Data Log
Figure 30 - Data Log WEB Applet (typical)
The controller normally logs data once every 5 minutes (default).  It logs the following 
parameters:
•  Voltage
•  Rectifier Current
•  Load Current
•  Battery Current
•  Battery Temperature 1
•  Battery Temperature 2 (not used on X75)
•  External Temperature
•  Controller Temperature
•  Number of rectifiers
•  Analog 1-4 (not used on X75)
•  Digital inputs (only digital input 1 is used on X75)
•  Free RAM.
The log is able to hold 8640 records which allows for 30 days of continuous data 
recording at 5 minute intervals.
The logging time can be adjusted to suit the application.  The choices are: 1 minute, 
5 minutes, 10 minutes, 30 minutes or 1 hour.  This can be adjusted using the 
Logging Time combo-box at the top of the applet.  To send the updated selection 
to the controller click the UPDATE LOGGING TIME button at the bottom.  An