Unique Broadband Systems Ltd. DRU2KW User Manual

Page of 64
Page 48
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
13.7  Alarm Log
Figure 29 - Alarm Log WEB Applet (typical)
The alarm log page shows details of historical alarms detected by the controller.  The 
colored indicators denote the following alarm levels:
Green
 – Alarm cleared
Yellow
 –Minor alarm condition
Red
 – Major alarm condition
Blue
 – Alarm condition but not configured as major or minor alarm.
A major or minor condition is configured by the alarm matrix outputs setting the 
major or minor LEDs.  If neither of these are configured for an alarm state but there 
are other outputs (other LEDs, relays, emails, buzzer) then the indicator in the alarm 
log will be blue.
Most of the alarm conditions should be self explanatory and are matched to the 
inputs of the alarm matrix.  The alarm log will also show an entry when the controller 
enters a reboot.
To refresh the display click the REFRESH button.  The applet automatically loads 
the alarm history when it is first run.  This takes a couple of seconds to load from 
the controller.
To clear the alarm log entirely from the controller, click the CLEAR button.  This 
requires an administrator level password.