Schneider Electric Industries SAS 01-EM43 User Manual
Chapter 3 - Commissioning
EM4300 series user manual
14
7EN02-0356-00
2. Swing the meter downward and push the bottom part of the meter until you hear an
audible click and the meter locks in place.
**ADD GRAPHIC HERE**
Removing the meter
1. Insert a flat-tip screwdriver into the DIN release clip. Pull up on the spring-loaded
clip until it clears the DIN rail edge.
**ADD GRAPHIC HERE**
2. Swing the meter out and downwards to remove the meter.
**ADD GRAPHIC HERE**
Meter wiring
The meter is intended for use with 4-wire 3-phase with neutral electrical systems. For
wiring instructions and safety precautions, see the meter installation sheet that was
shipped with your meter, or download a copy at www.schneider-electric.com.
wiring instructions and safety precautions, see the meter installation sheet that was
shipped with your meter, or download a copy at www.schneider-electric.com.
***ADD GRAPHIC AND ZOOM IN TO SPECIFIC LOCATIONS SUCH AS THE
VOLTATE INPUT TERMINALS, WHERE FERULLES NEED TO BE INSTALLED,
ETC***
VOLTATE INPUT TERMINALS, WHERE FERULLES NEED TO BE INSTALLED,
ETC***
Use the meter installation sheet when wiring the meter.
Voltage input protection
The meter’s voltage inputs must be wired to fuses/breakers and a disconnect switch.
•
Clearly label the device’s disconnect circuit mechanism and install it within easy
reach of the operator.
reach of the operator.
•
The fuses / circuit breakers must be rated for the installation voltage and sized for
the available fault current.
the available fault current.
•
Fuse for neutral terminal is required if the source neutral connection is not grounded.
See the meter installation sheet for fuse ratings.
Control power wiring
No additional wiring is required. The meter is powered from its L1-N voltage connection.