Eaton Power-Sure 700 TBL-045K-6 Leaflet
Product codes
TBL-045K-6
Technology
Tap changer
Input voltage range
+10% to -20%
Output voltage range
±3% typical
Input frequency range
47-53 Hz for 50 Hz models, 57-73 Hz for 60 Hz models
Efficiency
97% typical, 95% minimum
Load power factor
0.6 leading to 0.6 lagging
Common-mode noise attenuation
140 dB
Normal-mode noise attenuation
-3 dB @ 1000 Hz, -40 dBA per decade
Total harmonic distortion
Less than 1% added
Correction time
1 cycle typical, 1.5 cycle maximum
Overload rating
200% for 10 seconds, 1000% for 1 cycle
Overvoltage protection
Automatic electronic shutdown if output voltage exceeds +10% for 6 seconds (adjustable)
EnvironmEnts
Indicator lights
Indicator lights
Three green lights indicate regulated voltage on each phase. A fourth red light indicates an overtemperature condition
Audible noise
Less than 50 dBA @1 meter (depending on size)
Operating temperature
-10°C to +40°C
Altitude
Up to 10,000 ft
standards
Safety agency
Safety agency
UL 1012, CSA, FCC Cat. A
Surge suppression
Meets ANSI/IEEE Standard C62.41-1991
Warranty
One year
*Due to continuing product improvement programs, specifications are subject to change without notice.
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
www.eaton.com/powerquality
CANADA
Ontario: 416.798.0112
LATIN AMERICA
Brazil: 55.11.3616.8500
Caribbean: 1.949.452.9610
México & Central America:
52.55.9000.5252
South Cone: 54.11.4343.6323
EUROpE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.0.7841.604.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
portugal: 55.11.3616.8500
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA pACIFIC
Australia/NZ: 61.2.9693.9366
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.4223.2300
Singapore/SEA: 65.6829.8888
Eaton, power-Sure and powerChain
Management are tradenames, trademarks
and/or service marks of Eaton Corporation.
All other trademarks are the property
of their respective owners.
©2009 Eaton Corporation
All Rights Reserved
printed in USA
pOWSR700FXA
July 2009
tEchnical spEcifications*
powEr-surE 700 powEr conditionErs (thrEE-phasE)
Part Number
kVA
Input voltage
Output voltage
Output
distribution
Cabinet size
(H x W x D, in)
Weight (lb)
T_ _-010k-_
10
208/240/480
208Y/120
Hardwire
30.0 x 21.5 x 29.0
440
T_ _-015k-_
15
208/240/480
208Y/120
Hardwire
30.0 x 21.5 x 29.0
520
T_ _-025k-_
25
208/240/480/600
208Y/120
Hardwire
44.0 x 21.5 x 29.0
700
T_ _-030k-_
30
208/240/480/600
208Y/120
Hardwire
44.0 x 21.5 x 29.0
720
T_ _-045k-_
45
208/240/480/600
208Y/120
Hardwire
44.0 x 45.0 x 29.0
950
T_ _-050k-_
50
208/240/480/600
208/120-480/277
Hardwire
44.0 x 45.0 x 29.0
970
T_ _-075k-_
75
480/600
208/120-480/277
Hardwire
44.0 x 45.0 x 29.0
1100
T_ _-100k-_
100
480/600
208/120-480/277
Hardwire
44.0 x 45.0 x 29.0
1660
T_ _-125k-_
125
480/600
208/120-480/277
Hardwire
44.0 x 45.0 x 29.0
1980
T_ _-150k-_
150
480/600
208/120-480/277
Hardwire
44.0 x 45.0 x 29.0
2200
T_ _-225k-_
225
480/600
208/120-480/277
Hardwire
77.0 x 56.0 x 41.5
3300
T_ _-300k-_
300
480/600
208/120-480/277
Hardwire
77.0 x 56.0 x 41.5
4000
®
®
Part #T__ __ -
010k
- __
Input options
B=208 Vac, C=240 Vac,
D=480 Vac, E=600 Vac
B=208 Vac, C=240 Vac,
D=480 Vac, E=600 Vac
Output options
L=208/120 Vac (wye) output
N=480/277 Vac (wye) output
L=208/120 Vac (wye) output
N=480/277 Vac (wye) output
Frequency rating
6=60 Hz; 5=50 Hz
6=60 Hz; 5=50 Hz
• 75–300 kVA are available with 480/600V input only; requires
an additional auto-transformer for lower input voltage
• Listings - UL listed, CSA Certified, except for 600V: no UL,
CSA on 600V units
• For output distribution option, call factory
• K factor rated units available on request
• K factor rated units available on request