Eaton TPC2234-3866 Catalog

Page of 48
eaton corporation Enclosure Power Distribution Units
28
Indus
tr
ial ePDUs
Intelligent Power Control IPC3600 Series
(12) Indicator lights
• Main power system on
• Power on to outlets 1-8
• Two data and ethernet link
EMI/RFI filtering
•  Common mode - line to ground
•  Differential mode -line to line
•  Filtered inlet isolates noise before entering the system
•  Refer to chart 4 on page 40
 
 Spike/surge suppression
•  Line to neutral (or line)
•  Refer to chart 1 on page 40
Serial/ethernet
•   Serial RS232 via RJ22 connector on the rear. 6’ RJ22 to DB9 
cable included
•   Serial baud rate is 9600 default or  38,400 maximum
•   Ethernet (10/100) network via RJ45 connector on the rear. 6’ 
network cable included 
•   Network setup allows DHCP or any static public/private IP 
address
Software interfaces
•   Web interface provides a graphic control interface through a 
Web browser
•   Telnet interface provides a text menu control interface with any 
terminal emulation software  
•   SNMP allows read/write capability with trapping
•   Email notification system provides email alerts or logs showing 
user activity
•   Serial interface provides a text menu control interface with any 
terminal emulation software
•   FTP utility allows firmware upgrades 
 Software security
•   User name/password security
•   Settings allow the administrator to disable unused interfaces
Software features
•   Administrator and multiple users can be configured
•   User level access can be limited to specific outlets
•   Unit and outlet names can be configured
•   Outlet groups can be created to perform an action on multiple 
outlets
•   Outlet control includes individual, group and all outlet global 
control
•   Outlet actions include on or off and reboot
•   Global sequence allows all the outlets to be turned on or off in 
a preset sequence up to 999 seconds
•   Outlet reboot automatically turns an outlet off and back on with 
one command at a preset time up to 999 seconds
•   Email notification allows up to two email addresses to receive 
notifications of alerts or events
Auto-event scheduling
Administrator can configure on or off events for outlets or groups. 
The event occurs at the preset time daily or weekly. 
IPC36XX
Front view
Rear view
IPC3601
Rear view
IPC3602
Catalog Number
Full Load
Ethernet/
Serial
Receptacles
Circuit 
Breaker
EMI/RFI 
Filter
Surge  
Suppression
Input 
Plug
Cord (ft)
Dimensions  
(H x W x D, in)
IPC3601
1920 VA @ 120V~
3840 VA @ 240V~
Yes
(8) C13
(1) 20A
20A
Yes
C20 Inlet
Not 
Included
1.7 x 19.0 x 19.5
IPC3602
1920 VA
Yes
(8) 5-15R
(1) 20A
20A
Yes
C20 Inlet
Not 
Included
1.7 x 19.0 x 19.5
IPC3601-F3-3316
5760 VA
Yes
(8) C13
(2) 15A
No
Yes
L6-30P
10
1.7 x 19.0 x 19.5