29
(6) Indicator lights
• (1) Main power 
• (1) Data light
• (4) Power on to outlets 1-4
Communications
•  RS232, Serial: 9600 baud only
•  Optional ethernet control via RJ45 connector (add -NET  
to part number)
•  Data terminal emulation software is required to communicate 
with the IPC internal command codes such a telnet or 
hyperterminal 
EMI/RFI filtering
•  Common mode - line to ground
•  Differential mode - line to line
•  Refer to chart 2 on page 40
 Spike/surge suppression
• L-N, L-G, N-G
•  Refer to chart 1 on page 40
Outlet status
Query the IPC for Outlet and Watchdog status, i.e. outlets are (on 
or off)
Multiple time delay (MTD)
•  Turn outlets on or off at one time
•  Sequence power up and power down to outlets 1 - 4 with a 
four-second time delay (factory set)
•  Set power on sequence to any combination of outlets
•  Set the MTD timing from one second to 999 seconds,  
i.e. 009 = 9 seconds
Password protection
For added security, a password feature is included which allows 
you to assign a three alphanumeric character password
Addressing
 The IPC comes with a default address but you can also create your 
own with any four alphanumeric characters
Watch-dog/auto-reboot
•   The IPC monitors the control connection and automatically 
reboot itself if the connection locks up. The auto-reboot is 
activated by the time-out period running down to zero. When 
this occurs the IPC shuts down all outlets for four seconds and 
restart in the default or user defined sequence
•   Set the time out period to any number 0-9 where each digit 
represents 30 seconds, i.e. 3 = 120 seconds (user defined)
Commands available
• All outlets on/off
• Individual outlet on/off
•  Set up and sequence on/off all outlets
•  Create password and unit address
•  Name outlets with eight character name
•  Set up, enable or disable Watchdog
•  Display outlet and Watchdog timer status
Intelligent Power Control  IPC3400 series
Catalog Number
Full Load
Receptacles EMI/RFI 
Filter
Surge  
Suppression Cord (ft)
Power 
Input 
Plug
Serial Control 
(RS232)
Ethernet 
Control
Dimensions  
(H x W x D, in)
IPC3400-A1
1440 VA
(4) 5-15R
15A
270V
9
5-15P
Yes
No
3.4 x 9.0 x 5.8
IPC3400-A1-NET
1440 VA
(4) 5-15R
15A
270V
9
5-15P
Yes
Yes
3.4 x 9.0 x 5.8
IPC3400-AB
1440 VA/2880 VA
(4) C13
15A
270V
8
C14
Yes
No
3.4 x 9.0 x 5.8
IPC3400-AB-NET
1440 VA/2880 VA
(4) C13
15A
270V
8
C14
Yes
Yes
3.4 x 9.0 x 5.8
Indus
trial ePDUs
Front view
Rear view
IPC3400-A1-NET