Moxa ioLogik E1210 IOLOGIK E1210 User Manual

Product codes
IOLOGIK E1210
Page of 6
2
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Remote I/O
ioLogik E1212 Specifications
ioLogik E1211 Specifications
ioLogik E1210 Specifications
Inputs and Outputs
Digital Inputs: 16 channels
Isolation: 3K VDC or 2K Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact: 
NPN (DI to GND): 
 • On: 0 to 3 VDC 
 • Off: 10 to 30 VDC 
Inputs and Outputs
Digital Outputs: 16 channels
Isolation: 3K VDC or 2K Vrms
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Inputs and Outputs
Digital Inputs: 8 channels
Configurable DIOs: 8 channels
Isolation: 3K VDC or 2K Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact: 
NPN (DI to GND): 
 • On: 0 to 3 VDC 
 • Off: 10 to 30 VDC 
PNP (DI to GND): 
 • Off: 0 to 3 VDC 
 • On: 10 to 30 VDC
Common Type: 8 points per COM
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
PNP (DI to GND): 
 • Off: 0 to 3 VDC 
 • On: 10 to 30 VDC
Common Type: 8 points per COM
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Power Requirements
Power Consumption: 110 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 671,345 hrs
Database: Telcordia (Bellcore)
Power Requirements
Power Consumption: 208 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 923,027 hrs
Database: Telcordia (Bellcore)
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-Voltage Protection: 45 VDC
Over-Current Protection: 2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Power Requirements
Power Consumption: 155 mA @ 24 VDC
MTBF 
(mean time between failures)
Time: 561,930 hrs
Database: Telcordia (Bellcore)