Moxa ioLogik E1210 IOLOGIK E1210 User Manual
Product codes
IOLOGIK E1210
3
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Remote I/O
ioLogik E1214 Specifications
Inputs and Outputs
Digital Inputs: 6 channels
Relay Outputs: 6 channels
Isolation: 3K VDC or 2K Vrms
Relay Outputs: 6 channels
Isolation: 3K VDC or 2K Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact:
NPN (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
PNP (DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type: 6 points per COM
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact:
NPN (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
PNP (DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type: 6 points per COM
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Relay Output
Type: Form A (N.O.) power relay
Contact Current Rating:
Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Breakdown Voltage: 500 VAC
Relay On/Off Time: 1500 ms (max.)
Initial Insulation Resistance: 1000 M ohms (min.) @ 500 VDC
Mechanical Endurance: 5,000,000 operations
Electrical Endurance: 100,000 operations @ 5 A resistive load
Contact Resistance: 100 m ohms (max.)
Pulse Output: 0.3 Hz at rated load
Contact Current Rating:
Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Breakdown Voltage: 500 VAC
Relay On/Off Time: 1500 ms (max.)
Initial Insulation Resistance: 1000 M ohms (min.) @ 500 VDC
Mechanical Endurance: 5,000,000 operations
Electrical Endurance: 100,000 operations @ 5 A resistive load
Contact Resistance: 100 m ohms (max.)
Pulse Output: 0.3 Hz at rated load
Note: Ambient humidity must be non-condensing and remain between 5 and
95%. The relays of the ioLogik E1214 may malfunction when operating in high
condensation environments below 0° Celsius.
Power Requirements
Power Consumption: 188 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 808,744 hrs
Database: Telcordia (Bellcore)
Database: Telcordia (Bellcore)
Inputs and Outputs
Digital Inputs: 8 channels
Digital Outputs: 4 channels
Digital Input/Output (configurable by jumper): 4 channels
Isolation: 3K VDC or 2K Vrms
Digital Outputs: 4 channels
Digital Input/Output (configurable by jumper): 4 channels
Isolation: 3K VDC or 2K Vrms
Digital Input
Sensor Type: NPN, PNP, and dry contact
I/O Mode: DI or event counter
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact:
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Common Type: 12 points per COM
Counter/Frequency: 250 Hz, power off storage
I/O Mode: DI or event counter
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact:
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Common Type: 12 points per COM
Counter/Frequency: 250 Hz, power off storage
Digital Output
I/O Mode: DO or Pulse Output
I/O Type: Source
Current: 500 mA per channel
Voltage: 15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4
DO channels)
Pulse Wave Width/Frequency: 1 ms/500 Hz
Over-Voltage Protection: 41 VDC
Over-Current Limit: 1.5 A per channel @ 25°C
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Output Current Rating: 1.5 A per channel
I/O Type: Source
Current: 500 mA per channel
Voltage: 15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4
DO channels)
Pulse Wave Width/Frequency: 1 ms/500 Hz
Over-Voltage Protection: 41 VDC
Over-Current Limit: 1.5 A per channel @ 25°C
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Output Current Rating: 1.5 A per channel
Power Requirements
Power Input: 24 VDC nominal, 12 to 36 VDC
Power Consumption: 130 mA typical @ 24 VDC
Power Consumption: 130 mA typical @ 24 VDC
ioLogik E1213 Specifications