Power Sub-system 
Intel
®
 Entry Server Chassis SC5299-E TPS 
  
Revision 
3.1 
Intel order number D37594-005 
30 
Table 27. AC Line Dropout/Holdup 
Output Wattage 
Loading 
Holdup Time 
412.5 W 
75% 
20 msec 
550 W 
100% 
12 msec 
 
2.2.2.5.1 
AC Line 5VSB Holdup 
The 5VSB output voltage stays in regulation under its full load (static or dynamic) during an AC 
dropout of 70-ms min (=5VSB holdup time) whether the power supply is in the ON or OFF state 
(PSON asserted or de-asserted). 
2.2.2.6 
Power Recovery 
The power supply recovers automatically after an AC power failure. AC power failure is defined 
to be any loss of AC power that exceeds the dropout criteria. 
2.2.2.6.1 
Voltage Brown Out 
The power supply complies with the limits defined in EN55024: 1998 using the IEC 61000-4-
11:1995 test standard and performance criteria C defined in Annex B of CISPR 24. 
In addition, the power supply meets the following Intel Requirement: 
A continuous input voltage below the nominal input range shall not damage the power supply or 
cause overstress to any power supply component. The power supply must be able to return to 
normal power up state after a brownout condition. Maximum input current under a continuous 
brownout shall not blow the fuse. The power supply should tolerate a 3min ramp from 90VAC 
voltage to 0VAC after the components have reached a steady state condition. 
2.2.2.6.2 
Voltage Interruptions 
The power supply complies with the limits defined in EN55024: 1998 using the IEC 61000-4-
11:1995 and the level 3 test standard and performance criteria C defined in Annex B of CISPR 
24. 
2.2.2.7 
AC Line Inrush 
AC line inrush current does not exceed 50A peak for up to one-quarter of the AC cycle, after 
which, the input current should be no more than the specified maximum input current. The peak 
inrush current is less than the ratings of its critical components (including input fuse, bulk 
rectifiers, and surge limiting device). 
The power supply must meet the inrush requirements for any rated AC voltage, during turn on at 
any phase of AC voltage, during a single cycle AC dropout condition, as well as upon recovery 
after AC dropout of any duration, and over the specified temperature range (T
op
). It is 
acceptable that AC line inrush current may reach up to 70A peak for up to 1 ms