Intel SC5299WS User Manual

Page of 154
Power Sub-system 
Intel
®
 Entry Server Chassis SC5299-E TPS 
  
Revision 
3.1 
Intel order number D37594-005 
48 
Duration 
Sag 
Operating AC 
Voltage 
Line Frequency 
Loading 
Performance Criteria 
> 1 AC cycle 
>10% 
Nominal AC 
Voltage ranges 
50/60Hz 
100% 
Loss of function acceptable, self 
recoverable 
Table 54. AC Line Surge Transient Performance 
Duration 
Surge 
Operating AC Voltage 
Line Frequency 
Performance Criteria 
Continuous 
10% 
Nominal AC Voltages 
50/60Hz 
No loss of function or performance 
0 to ½ AC 
cycle 
30% 
Mid-point of nominal AC 
Voltages 
50/60Hz 
No loss of function or performance 
 
2.3.2.5 
AC Line Fuse 
The power supply has a single line fuse on the line (hot) wire of the AC input. The line fusing is 
acceptable for all safety agency requirements. The input fuse is a slow blow type. AC inrush 
current will not cause the AC line fuse to blow under any conditions. All protection circuits in the 
power supply will not cause the AC fuse to blow unless a component in the power supply has 
failed. This includes DC output load short conditions. 
2.3.2.6 
AC In-rush 
AC line in-rush current does not exceed 55A peak for up to one-quarter of the AC cycle, after 
which the input current is no more than the specified maximum input current. The peak in-rush 
current is less than the ratings of its critical components (including input fuse, bulk rectifiers, and 
surge limiting device). 
The power supply meets the in-rush requirements for any rated AC voltage, during turn on at 
any phase of AC voltage, during a single cycle AC dropout condition, as well as upon recovery 
after AC dropout of any duration, and over the specified temperature range (T
op
). 
2.3.2.7 
Susceptibility Requirements 
The power supply meets the following electrical immunity requirements when connected to a 
cage with an external EMI filter that meets the criteria defined in the SSI document EPS Power 
Supply Specification.  
Table 55. Performance Criteria 
Level 
Description 
The apparatus shall continue to operate as intended. No degradation of performance. 
The apparatus shall continue to operate as intended. No degradation of performance 
beyond spec limits. 
Temporary loss of function is allowed provided the function is self-recoverable or can be 
restored by the operation of the controls.