Hitachi RAF-35RPA RAF35RPA User Manual
Product codes
RAF35RPA
CAPACITIES AND SELECTION DATA
4-9
4.2.
CAPACITY CHARACTERISTIC CURVES FOR MONOZONE/MULTIZONE
The following charts show the characteristics of outdoor unit capacity, which corresponds with the operating ambient
temperature of outdoor unit.
Conditions:
Conditions:
①
Pipe length / height difference : 7.5m / 0m
③
Compressor at rated inverter frequency
②
Indoor fan speed at High mode
④
Capacity loss due to white frost and defrost operation is not included.
4.2.1. RAI-25RPA/RAC-25NPA
COOLING [50Hz, 230V]
INDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB EDB
-10
21
27
32
35
40
43
°C
°C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
12.0 18 2649 1991 528 2200 1947 460 2036 1797 542 2050 1820 639 1975 1740 667 1850 1640 716 1775 1560 744
14.0 20 2649 1991 528 2364 1947 460 2200 1816 548 2200 1820 646 2125 1760 674 1975 1640 723 1900 1580 758
16.0 22 2649 2119 536 2528 1947 466 2340 1816 555 2350 1820 653 2275 1760 688 2125 1640 737 2050 1580 765
18.0 25 2840 2272 545 2691 2116 472 2481 1966 561 2500 1980 660 2400 1900 688 2250 1780 744 2150 1700 771
19.0 27 2936 2349 553 2785 2228 478 2574 2060 567 2600 2080 667 2500 2000 695 2350 1880 744 2250 1800 771
22.0 30 3255 2323 553 3089 2209 478 2855 2041 567 2875 2060 674 2775 1980 702 2500 1920 771 2325 1880 813
24.0 32 3479 2323 561 3300 2209 484 3043 2041 574 3075 2060 674 2950 1980 709 2600 1960 792 2375 1940 841
14.0 20 2649 1991 528 2364 1947 460 2200 1816 548 2200 1820 646 2125 1760 674 1975 1640 723 1900 1580 758
16.0 22 2649 2119 536 2528 1947 466 2340 1816 555 2350 1820 653 2275 1760 688 2125 1640 737 2050 1580 765
18.0 25 2840 2272 545 2691 2116 472 2481 1966 561 2500 1980 660 2400 1900 688 2250 1780 744 2150 1700 771
19.0 27 2936 2349 553 2785 2228 478 2574 2060 567 2600 2080 667 2500 2000 695 2350 1880 744 2250 1800 771
22.0 30 3255 2323 553 3089 2209 478 2855 2041 567 2875 2060 674 2775 1980 702 2500 1920 771 2325 1880 813
24.0 32 3479 2323 561 3300 2209 484 3043 2041 574 3075 2060 674 2950 1980 709 2600 1960 792 2375 1940 841
HEATING [50Hz, 230V]
INDOOR
OUTDOOR TEMPERATURE (°CDB)
EDB
-15
-10
-7
-5
0
7
10
15
°C
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
16
1260
0 696 1995
0 714 2275
0 745 2461
0 765 2996
0 856 3539
0 868 3861
0 891 4456
0 935
18
1243
0 705 1978
0 724 2253
0 761 2436
0 785 2965
0 878 3521
0 912 3847
0 931 4438
0 979
20
1225
0 714 1960
0 733 2233
0 773 2415
0 799 2940
0 893 3500
0 940 3763
0 973 4410
0 1025
22
1208
0 724 1943
0 743 2205
0 789 2380
0 820 2909
0 915 3479
0 978 3805
0 1009 4389
0 1067
24
1190
0 733 1925
0 752 2185
0 804 2359
0 839 2884
0 936 3458
0 1015 3784
0 1047 4326
0 1110
EWB : Evaporator Wet Bulb temperature (
C)
TC : Total Capacity (W)
EDB : Evaporator Dry Bulb temperature (
C)
SHC : Sensible Heating Capacity (W)
(
CDB) : Outdoor Unit Inlet Air Dry Temperature (
C)
PI : Power Input