1-24
 
 
•  Please decide the type of dry contact you will be using and set the position of the DIP Switch No. 2 and 3 accordingly 
 
[1] CHECK DRY CONTACT OF CARD KEY UNIT 
 
[2] SET THE POSITION OF DIP SWITCH 
 
AIR CONDITIONER 
Standby 
AIR CONDITIONER 
Operating 
 
POSITION CONDITION OF DIP SWITCH 
CARD KEY 
(Door 
Switch) 
REMOVE 
INSERT 
 
INITIAL CONDITION  
(CARD KEY NO USE) 
 
 
 
 
Contact 
type a 
 
OPEN 
CLOSE 
 
 
 
 
Contact 
type b 
 
CLOSE 
OPEN 
 
 
 
 
 
 
 
After all connection has been done as below diagram, ON the breaker and push ON button of wireless remote controller or 
wired remote controller to operate the air conditioner unit. 
•  When the CARD KEY is in insert condition, the air conditioner operation is allowable by remote controller. 
•  When the dry contact switch on the Card Key Unit is open (refer to diagram below for contact type a), the unit stops to  
operate (it takes 10 seconds to stop the unit operation after the dry contact switch on the card key turns off) and vice 
versa. 
•  When the card key is removed from the Card Key Unit, the wireless remote controller cannot be used. 
•  When the card key is removed from the Card Key Unit, the wired remote controller LCD display is activated; however it    
has no control over the unit. 
•  The suitable accessory Connecting Cord (accessory code#: SPX-WDC1 or SPX-WDC2) need to be used to 
connect the Card Key Unit’s dry contact switch to the connector on the control board of the indoor unit. Please refer to 
Table 1 to select suitable accessory code# for the concerning indoor model. 
 
Example of wiring connection to Card Key Unit will be as below (reference only) 
CARD KEY UNIT (Prepared by INSTALLER) 
AIR CONDITIONER INDOOR PCB 
 
 
AC 
POWER 
SUPPLY 
① Connecting Cord to PCB: 
SPX-WDC1 or SPX-WDC2 
(refer to Table 1) 
② Contact with sleeve 
CN6 or CN9 
(Refer to Table 1) 
DIP SW Label 
(Refer to Table 1) 
Dry contact 
Card sensor 
indicator 
HI Input Active 
LO Input Active