Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
10-37 
 
 
 
Material of the Wall, Frame 
Flammable 
Non-flammable 
Min 100cm 
Min 10cm 
Min 60cm 
Min 5cm 
f) 
If decided to keep the flange at discharge side, fix 
screw ② at 8 positions. However, if decided not to 
keep the flange, remove 4 screws that fixed to the 
flange. 
Fix in factory 
 
g)  Adjusting of the Unit Level 
i) 
Check  to ensure that the foundation is flat, 
taking into account the maximum foundation 
gradient. If not, it will cause malfunction of 
float switch or no operation. Subsequently, 
drain water will drop from ceiling 
 
ii) 
The unit should be installed so that the rear 
side of the unit is slightly (0mm to 5mm) lower 
than the fronts side, in order to prevent 
incorrect positioning of the drain discharge. 
iii)  Tighten the bolts of the sling nuts with the 
suspension brackets after adjustment is 
completed. Special plastic paint must be 
applied to the bolts in order to prevent them 
from loosening. Keep the unit as well as 
relevant equipment covered with vinyl  
h)  Connecting Return Duct and Supply Duct 
i) 
The return duct should be connected with the 
indoor through canvas ducts between inlet 
side of the indoor unit and ceiling of the room. 
The supply duct should be connected with the 
indoor unit through canvas ducts. In order to 
avoid abnormal sound vibration. The unit is 
equipped with a pre-drilled duct flange for the 
return and supply duct connection. 
ii) 
Attach the vibration proof rubber to Sling bolt 
in order to avoid abnormal sound vibration. 
iii)  Natural frequency is 9 to 21Hz 
iv)  Duct material should be non-inflammable 
material. 
v)  Perform the heat insulation work over the 
duct and the duct flange for dew protection. 
 CAUTION 
• 
If a lower sound level is further required, install 
silencer (field-supplied) 
• 
The facility design should be “Unit External Static 
Pressure = Duct Pressure Loss Suction / Discharge 
Loss”. If the duct pressure loss becomes under to 
the unit external static pressure, air speed will get 
larger and lead to the occurrence of loud noise, 
splashing water and the trigger of motor protection 
mechanism. If the unit external static pressure 
becomes under to the duct pressure loss, some 
problems such as inability to change the air speed 
may occur. Set the air flow control damper or shift 
the static pressure control switch to adjust to get 
almost equal level between the external static 
pressure and the duct pressure loss. (See “Setting 
of External Pressure” section for the details) 
• 
Basically this unit is designed to install the ducts on 
the inlet side and the outlet side. Ask for more 
information for using the return ducts in the ceiling. 
 
• 
Select the indoor unit position, fixing direction of air 
outlet so  that cool/hot air reaches all the room. 
Standard position of the indoor unit is with the wall 
side on the ceiling.  
• 
Remove the factory fitted filter and filter holders 
before installing of full duct type. 
 
Unit 
5m
m
 
Air filter 
Air filter 
removing 
direction 
A
 
Out
do
or
 A
ir
 
(wit
h A
ir
 
Filt
er
Da
mp
er f
o
adjus
ting
 a
ir
 
volum
S
ilen
cer
 
A
ir
 Inle
C
an
va
s D
u
c
C
an
va
s D
u
ct
 
S
er
vi
ce A
cc
es
s p
an
el
 
(450m
m
x450
m
m
H
or
izo
nt
al
 
A
ir
 Out
le
S
ilen
cer
 
The
rm
al ins
ul
at
ion
 
Da
mp
er f
o
r f
in
adjus
ting
 a
ir
 
volum