Enlogic EN1111 Data Sheet

Page of 2
The Critical Component
 
 
 
 
 
      
 
 
 
 
                      
 
LT-50513-A1 
 
 
Model: EN1120, 1111, 1112 
Specifications
 
Electrical
 
Acceptable input voltage 
 
380–415 VAC +6%, -10% 
Input current (phase) 
 
32 A  
Input frequency 
 
50 Hz 
Input power 
 
21.04–23.05 kVA 
Input plug 
32 A, 5-pin IEC-60309, type 532P6 
Input phases 
3 phase 
Output voltage 
 
220–240 VAC 
Maximum output current (phase) 
 
32 A 
Maximum output current (circuit breaker bank) 
16 A 
Maximum output current (outlet) 
 
IEC C13: 10A per outlet, 16A per gang 
IEC C19: 16A 
 
Overload protection (internal) 
 
Six (6) 16 A, 1-pole hydraulic-magnetic circuit breakers
 
Outlet Configuration 
EN1120: (24)C13, (12)C19  
EN1112: (48)C13 
EN1111: (30)C13, (12)C19         
Physical
 
Dimensions (H x W x D) 
EN1120: 173.0 x 5.5 x 5 cm 
EN1112: 182.6 x 5.5 x 4.4 cm 
EN1111: 182.6 x 5.5 x 5 cm 
Weight 
EN1120: 7.5 Kg 
EN1112: 8.5 Kg  
EN1111: 8.5 Kg 
Shipping dimensions (H x W x D) 
 
EN1120: 196.5 x 17.0 x 11.5 cm 
EN1112: 206.0 x 17.0 x 11.5 cm  
EN1111: 206.0 x 17.0 x 11.5 cm 
Shipping Weight  
EN1120: 9.5 Kg 
EN1112: 10.5 Kg  
EN1111: 10.5 Kg 
Power cord length   
3.0 m (factory standard) or 1.0 – 5.0 m (user specified) 
Environmental
 
Maximum elevation, above MSL (Operating/Storage) 
0–3,000 m / 0–15,000 m 
Temperature (Operating/Storage) 
–5 to 60°C / –25 to 65°C 
Humidity (Operating/Storage) 
 
5–95% RH, non-condensing 
Compliance
 
EMC verification   
EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 
Safety verification   
TÜV , CE , EN/IEC 60950-1 
Environmental Verification
 
ROHS, WEEE
 
 
 EN Series Product Data Sheet 
 
EnLogic Systems Europe, Ltd.         EnLogic Systems, LLC.           EnLogic Systems Asia Pacific, Ltd.  
Worcester 
                                Wildwood 
                               Tsim Sha Tsui 
United Kingdom WR1 2PG                          Missouri USA 63040                       Kowloon, Hong Kong 
sales@emea.enlogic.com 
www.enlogic.com