Enlogic EN1111 Hoja De Datos
The Critical Component
LT-50513-A1
Model: EN1120, 1111, 1112
Specifications
Electrical
Acceptable input voltage
380–415 VAC +6%, -10%
Input current (phase)
32 A
Input frequency
50 Hz
Input power
21.04–23.05 kVA
Input plug
32 A, 5-pin IEC-60309, type 532P6
Input phases
3 phase
Output voltage
220–240 VAC
Maximum output current (phase)
32 A
Maximum output current (circuit breaker bank)
16 A
Maximum output current (outlet)
IEC C13: 10A per outlet, 16A per gang
IEC C19: 16A
IEC C19: 16A
Overload protection (internal)
Six (6) 16 A, 1-pole hydraulic-magnetic circuit breakers
Outlet Configuration
EN1120: (24)C13, (12)C19
EN1112: (48)C13
EN1111: (30)C13, (12)C19
EN1112: (48)C13
EN1111: (30)C13, (12)C19
Physical
Dimensions (H x W x D)
EN1120: 173.0 x 5.5 x 5 cm
EN1112: 182.6 x 5.5 x 4.4 cm
EN1111: 182.6 x 5.5 x 5 cm
EN1112: 182.6 x 5.5 x 4.4 cm
EN1111: 182.6 x 5.5 x 5 cm
Weight
EN1120: 7.5 Kg
EN1112: 8.5 Kg
EN1111: 8.5 Kg
EN1112: 8.5 Kg
EN1111: 8.5 Kg
Shipping dimensions (H x W x D)
EN1120: 196.5 x 17.0 x 11.5 cm
EN1112: 206.0 x 17.0 x 11.5 cm
EN1111: 206.0 x 17.0 x 11.5 cm
EN1112: 206.0 x 17.0 x 11.5 cm
EN1111: 206.0 x 17.0 x 11.5 cm
Shipping Weight
EN1120: 9.5 Kg
EN1112: 10.5 Kg
EN1111: 10.5 Kg
EN1112: 10.5 Kg
EN1111: 10.5 Kg
Power cord length
3.0 m (factory standard) or 1.0 – 5.0 m (user specified)
Environmental
Maximum elevation, above MSL (Operating/Storage)
0–3,000 m / 0–15,000 m
Temperature (Operating/Storage)
–5 to 60°C / –25 to 65°C
Humidity (Operating/Storage)
5–95% RH, non-condensing
Compliance
EMC verification
EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3
Safety verification
TÜV , CE , EN/IEC 60950-1
Environmental Verification
ROHS, WEEE
EN Series Product Data Sheet
EnLogic Systems Europe, Ltd. EnLogic Systems, LLC. EnLogic Systems Asia Pacific, Ltd.
Worcester
Wildwood
Tsim Sha Tsui
United Kingdom WR1 2PG Missouri USA 63040 Kowloon, Hong Kong
sales@emea.enlogic.com
sales@emea.enlogic.com
www.enlogic.com