Lappkabel 00100004, Control Data Cable, , Grey Sheath 00100004 Data Sheet

Product codes
00100004
Page of 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
 
 
ÖLFLEX
®
  CLASSIC 100
 
 
DB 0010000               
valid from: 11.02.2013 
 
 
Originator:  ROKR / PDC
 
Approved:   HAPF / PDC 
Dokument: 
DB0010000EN 
Page 1 of 1 
All rights reserved acc. to DIN ISO 16016.  
PD 0019/2.2_11.10EN 
Application 
 
ÖLFLEX
 CLASSIC 100 cables are connecting- and control cables for occasional flexible use and fixed installation for medi-
um mechanical use. They are for use in dry, damp and wet rooms. They may only be installed outdoors with UV-protection 
and in observation of the temperature range. At room temperature they are generally resistant against acids, caustics solu-
tions and certain oils. ÖLFLEX
 CLASSIC 100 cables are used as supply and flexible connecting cable in machine tool manu-
facture, plant engineering, in power stations, in heating and air conditioning installations, etc. They are suitable for free non-
continuously recurring movement without tensile load or compulsory guidance.  
This cable is suitable for torsion application in wind turbines (WTG). The torsional load is limited to applications, as they 
typically occur in the loop of a wind turbine. 
 
 
Design 
Design 
 
based on EN 50525-2-51 resp. VDE 0285-525-2-51 / HD 21.13 S1 resp. VDE 0281-13 
 
Conductor 
 
bare copper, fine wire strand in acc. with IEC 60228  resp. VDE 0295, Class 5 
 
 
 
Core insulation 
 
PVC compound TI2 acc. to VDE 0207-363-3 with increased requirements 
  
 
acc. to Lapp specification 
 
Core identification 
 
with up to 5 cores are coloured-coded in acc. to HD 186 resp. VDE 0293 
 
 
or HD308S2 that is VDE 0293-308; cables with more than 5 cores are colour-coded in  
 
 
acc. to LAPP-ÖLFLEX colour-code. 
 
Outer sheath 
 
PVC compound TM2 acc. to VDE 0207-363-4-1 with increased requirements    
 
 
acc. to LAPP specification 
 
 
Electrical properties 
Nominal voltage 
 
0,5 mm
2
 to 1,5 mm
2
 :  
 
 
 
300 / 500 V 
 
 
from 2,5 mm
2
 :    
 
 
 
450 / 750 V 
 
 
from 2,5 mm
2
 , fixed and protected installation: 
600 / 1000 V 
 
 
Test voltage 
 
4000 V AC 
 
 
Mechanical and thermal properties 
Min. bending radius 
occasional flexing:   
15 x cable diameter 
 
 
 
fixed installation:    
  4 x cable diameter 
 
Temperature range 
occasional flexing:   
  -5 °C up to +70 °C max. conductor temp. 
 
fixed installation: 
-40 °C up to +80 °C max. conductor temp. 
 
Torsion movement in WTG  
TW-0 (5000 cycles at ≥ +5°C) 
TW-1 (2000 cycles at ≥ -20°C) 
± 150 °/m at 1 revolution per minute  
 
Flammability 
 
flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-2-1 
 
Tests 
 
acc. to IEC 60811 resp. VDE 0473-811, VDE 0472, EN 50395, EN 50396 
 
EC-Directives 
 
 
This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive) and 
2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).