UMG 96RM-M
Assembly
Installation location
The UMG 96RM-M is suitable for installation in perma-
nent, weatherproof switchboards. Conducting switch-
boards must be earthed.
Installation position
The UMG 96RM-M must be installed vertically in order 
to achieve sufficient ventilation. The clearance to the top 
and bottom must be at least 50 mm and 20 mm 
at the sides.
Front panel cutout
Cutout dimensions: 
92
+0.8
 x 92
+0.8
 mm.
m
Failure to comply with the minimum 
spacing can destroy the UMG 96RM-M 
at high ambient temperatures!
Fig. UMG 96RM-M 
installation location 
(rear view)
 
Mounting
The UMG 96RM-M is mounted on the switchboard 
by the side mounting brackets. These must be removed 
before using the device. Mounting is carried out 
by inserting and engaging the brackets.
Fig. UMG 96RM-M 
mounting bracket (side 
view)