UMG 96RM-M
M-Bus interface
The M-Bus interface is designed with the UMG 96RM-M 
as a  2-pole plug contact and communicates via the M-
Bus protocol.
The UMG 96RM-M loads the M-Bus with an M-Bus de-
vice load of 1.5 mA.
M-Bus interface, 
2-pole plug contact 
M+
M-
Cable connections
Twisted screened cable should be used for connections 
via the M-Bus interface.
•  Cable paths should be designed to be as short as 
possible.
•  Maintain as much distance as possible to power ca-
bles and to consumers (e.g. electrical motors, neon 
tubes, transformers).
•  In order to prevent cross currents in the bus, there 
should be no ground coupling, or a maximum of one 
instance of ground coupling.
•  Gather the cables mechanically above the earthing 
clamp in order to avoid damage due to cable move-
ments.
•  Use suitable cable glands to feed the cables into the 
cabinet - for example armoured conduit couplings.
2-pin connector with cable 
connection (
 
cable type: 2
 
x
 
0.75
 
mm
2
 
) via twin ferrules