UMG 96RM-M
Comparator
Two comparator groups, each with 
3 comparators, are available for 
monitoring limit values. The results 
from comparators A, B and C can 
be AND or OR linked. 
The linkage result from comparator 
group 1 can be assigned to digital 
output 1 and the linkage result from 
comparator group 2 is assigned 
to digital output 2.
Measured value (addr. 110)
Limit value (addr. 108)
Minimum turn-on time (addr. 111)
Lead time (addr. 112)
Operator ">=", "<" (addr. 113)
Comparator A
Measured value (addr. 116)
Limit value (addr. 114)
Minimum turn-on time (addr. 117)
Lead time (addr. 118)
Operator ">=", "<" (addr. 119)
Comparator B
Measured value (addr. 122)
Limit value (addr. 120)
Minimum turn-on time (addr. 123)
Lead time (addr. 124)
Operator ">=", "<" (addr. 125)
Comparator C
Comparator result (addr. 610)
Comparator result (addr. 611)
Comparator result (addr. 612)
Total running time
(addr. 5898)
Total running time
(addr. 5900)
Total running time
(addr. 5902)
Link the results from comparators A, B and C
Link the results from comparators A, B and C as AND or OR (addr. 107).
Comparator group 1
Linkage result (addr. 616)