Entes EPR-04S-96 Data Sheet

Page of 4
POWERMETER
EPR-04 / EPR-04S
7
POWERMETER
EPR-04 / EPR-04S
2
Reactive Energy Calculation Method Setting
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button (trAFo Ctr menu is displayed)
Press SET button (Calculation value “1” blinks)
Press set  button, CAL CLt is displayed. (Data is entered  but is
not activated yet. For activating the new data please follow the
below steps.
Press ESC button one by one until “SAUE  SEt  yES” is displayed.
Press SET button. When “SAUE  SEt  yES” is displayed, if you
press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.
By using UP-DOWN buttons, find “CAL CLt” menu.
By using UP-DOWN buttons, select energy calculation method.
ESC
SET
SET
SET
SET
SET
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons find “dE tý” menu.
Press SET button (First digit blinks.)
By using UP-DOWN buttons, enter the value to the first digit.
Press SET button (Second digit blinks)
In this menu, demand time is set between 1-60 minutes.
By using UP-DOWN buttons, enter the value to the  second digit.
Press SET button, “dE tý” is displayed. (Data is entered but is not
activated yet. For activating the new data please follow the below
steps).
Press ESC button one by one until (SAU E  SEt  yES) is displayed.
Press SET button. When “SAU E  SEt  yES” is displayed, if you press
ESC button or choose “no” option instead of “yES” option by using
UP-DOWN buttons, new data will be cancelled and previous value
will be activated.
Press SET button 3 seconds (trA Fo menu is displayed)
By using the UP-DOWN buttons
find the rES Et menu.
Press SET button.(rES Et HL menu
is displayed)
Press SET  button, (Data is entered
but is not activated yet.
For activating the new data please follow the below steps).
Press SET button. When “SAUE  SEt  yES” is displayed, if you press
ESC button or choose “no” option instead of “yES” option by using
UP-DOWN buttons, new data will be cancelled and previous value
will be activated.
By using the UP-DOWN buttons,
other parameters can be selected.
If you want to delete the value,
choose yEs, if not choose no.
Monitoring and Erasing of  minimum and maximum values:
In this menu, values of min., max., demand or energymeter’s are
erased. It saves the instantaneously measured min. and max. values
of EPR-04/04S into  its memory. Please kindly look at to the section
of FUNCTIONS OF  BUTTONS for min. and max. values.
SET
ESC
SET
SET
SET
Press ESC button one by one until “SAUE  SEt  yES” is displayed.
Programming the Turn Number:
Note: 
If the voltage transformer is not used between the system
and  EPR-04/04S, voltage transformer ratio is entered as ‘1’.
Example:
 If a voltage transformer which has a ratio of 34.5KV/100V
is used between the system and EPR-04/04S; Voltage transformer
ratio is entered as 345. (34500/100)
Voltage Transformer Ratio Setup
In this menu, voltage transformer ratio is set between
0000,1 - 4000,0.
Demand Time Setup:
This menu is available for CT-25 adapted devices. User enter
the turn number, which is the number of how many tour the current
cable has rounded into the CT-25. Numbers can be selected
between 1-20. Greater the number of turn means greater the
sensivity.
0
2
4
1
3
5
Description
It is the most preferred reactive power calculation
methode.
Total value of the multiplication of Vn and In values up
to 19 th harmonics. This calculation methode is mostly
preferred for network analysers.
S
V
n
.I
n
.sin(j
n
)
n=1
¥
Reactive Energy
(Q)
Digital Energymeter
(Each phase seperately)
Mechanical Energymeter
(Vectoral summation of 3-phase)
90° rotation of
voltage vector and
multiply with current
S
2
-P
2
S
2
-P
2
Power Triangle Methode : According to this methode;
Q =
(Q : Reactive power, S : Active power, P : Apparent power)
Three different methods exist for reactive energy calculation in
EPR-04/04S. Brief informations about these methods are explained
in below table.
Related values which must be entered in the menu are also
indicated in the table in order to select reactive power calculation
method for mechanical and digital energymeters.
Note:
 Measured electrical parameters which are saved to the memory are
not affected from the electric interruptions.
In the rES Et dE E-1 / E-2 menu; when you choose yES and quit from  all menus,
if you confirm the changes, min. and max. values of all parameters or values
of energymeters are erased at the same time. Follow the below steps in order
to erasing the values of min., max., E-1 and E-2
; In the measurement position.
PK 26 Box Connection Diagram
*Available only for EPR-04S
~
Un
TR
 A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+
_
L3
L2
L1
1A
- +
- +
(12-48V DC)
k
l
K
L
k
l
K
L
k
l
K
L
~
Un
TR
 A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+
_
Max: 30 VDC
L3
L2
L1
- +
- +
(12-48V DC)
1A
k
l
K
L
k
l
K
L
~
Un
TR
 A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+
_
Max: 30 VDC
L3
L2
L1
1A
- +
- +
(12-48V DC)
k
l
K
L
k
l
K
L
~
Un
TR
 A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+
_
Max: 30 VDC
N
L3
L2
L1
1A
- +
- +
(12-48V DC)
k
l
K
L
k
l
K
L
k
l
K
L
Auxiliary
Supply
Voltage Measuring Input Current Measuring Input
3 Phase neutral
L1
L2
L3
N
RS-485
1
2.00
120
2
1.00
60.0
3
0.66
40.0
4
0.50
30.0
5
0.40
24.0
6
0.33
20.0
7
0.28
17.1
8
0.24
15.0
9
0.22
13.3
10
0.20
12.0
11
0.18
10.9
12
0.16
10.0
13
0.15
9.23
14
0.14
8.57
15
0.13
8.00
16
0.12
7.50
17
0.11
7.05
18
0.11
6.66
19
0.10
6.31
20
0.10
6.00
Note: For CT-25 models:
Auxiliary
Supply
Voltage Measuring Input Current Measuring Input
3 Phase without neutral current input  with
Aron wiring configuration
L1
L2
L3
N
RS-485
N
Auxiliary
Supply
Voltage Measuring Input Current Measuring Input
3 Phase without neutral
L1
L2
L3
N
RS-485
N
Max: 30 VDC
Auxiliary
Supply
Voltage Measuring Input Current Measuring Input
3 Phase without neutral current input  with
Aron wiring configuration
L1
L2
L3
N
RS-485
N
k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.