Entes EPR-04S-96 Data Sheet

Page of 4
3
In this menu user password is defined and activated.  
You must define and activate a 4 digit user password for preventing
device settings from the illegal usage.
There are 2 sub menu under the Pýn menu.
This menu is used for changing the user password .
Note:
  Factory default value for user password is “0000”
For changing the user password;In the measurement mode,
Press SET button 3 seconds
(trA Fo menu is displayed)
Bu using UP-DOWN buttons
find  Pýn menu.
Press SET button (Pýn ACt ýUA tE
menu is displayed.)
By using the UP-DOWN buttons
find Pýn CHA ngE menu.
User password Setup:
Changing of User Password:
By using UP-DOWN-SET
button enter the new
password
By using UP-DOWN-SET
button reenter the new password.
Press SET button, Pýn CHA ngE is displayed. Data is entered  but is
not activated yet. For activating the new data please follow the below
steps).
Press ESC button one by one until (SAU  SEt  yES) appears at the
display.
Press SET button  when (SAU  SEt  yES) appears at the display. (When
SAU  SEt  yES appears at the display,If you Press  ESC button or
choose “no”  option instead of “yES” option, you quit from adjustment
menu without saving new settings and device continues   to work with
previous settings.
By using UP-DOWN-SET button enter the old password
ESC
SET
SET
SET
SET
SET
SET
SET
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons, find “Eng Cnt” menu.
Press SET button (”Eng Cnt E-1” menu is displayed)
SET
SET
Press SET  button, (Data is entered but is not activated yet.
For activating the new data please follow the below steps).
Press ESC button one by one until “SAUE  SEt  yES” is displayed.
Press SET button. When “SAUE  SEt  yES” is displayed, if you
press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.
By using UP-DOWN buttons, select “E-1” or “E-2”.
Press SET button.
SET
ESC
SET
SET
Activating the user password:
Press ESC button one by one until “SAU E  SEt  yES” is displayed.
Press SET button. When “SAU E  SEt  yES” is displayed, if you
press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.
Press SET button for 3 seconds (trA Fo menu is displayed)
Bu using UP-DOWN buttons, find “Pýn” menu.
Press SET button (“Pýn ACt IUA tE” menu is displayed)
Press SET button. First digit of the displayed value is blinking.
Enter the blinking digit value by scrolling UP/DOWN buttons.
Switch to the other digits by using SET button, use ESC button
to go to previous digit. After you entered the last digit press SET
button, “Pýn ACt oF” is displayed. “on” can be selected by
scrolling UP/DOWN buttons. (Data is entered but is not activated
yet. For activating the new data please follow the below steps).
POWERMETER
EPR-04 / EPR-04S
6
POWERMETER
EPR-04 / EPR-04S
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons, select “PUL SE rAt”,
“PUL SE o-1” or “PUL SE o-2”.
Press SET button.
By using UP-DOWN buttons, find “PULSE” menu.
Pulse Menu
Press SET button (”PUL SE rAt” menu is displayed)
Press SET  button, (Data is entered but is not activated yet.
For activating the new data please follow the below steps).
Press ESC button one by one until “SAU E  SEt  yES” is
displayed.
Press SET button. When “SAU E  SEt  yES” is displayed, if you
press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.
In this menu, three parameters can be selected : “PUL SE rAt”,
“PUL SE o-1”, “PUL SE o-2”
PUL SE rAt ýo : Pulse ratio can be set as :
1, 10, 100 (wh/VArh/VA); 1, 10, 100 (kwh/kVArh/kVA);
1 Mwh/MVArh/MVA.
SET
ESC
SET
SET
SET
SET
By using UP-DOWN buttons, type the  required value for
selected parameter.
Energy Counter (Eng Cnt) Menu
EPR-04/04S has 2 energy counters :
Energy counter 1 (E-1), Energy counter 2 (E-2).
“E-1 / E-2” have 4 parameters :
on : Activate “E-1 / E-2” counters for energy counting without depending
on any parameter.
ý-1 : Activate “E-1 / E-2” counters, when digital input 1 is on (=1).
ý-2 : Activate “E-1 / E-2” counters, when digital input 2 is on (=1).
E-2: “E-1” does not count when “E-2” is activated. (Only for “E-1”)
E-1: “E-2” does not count when “E-1” is activated. (Only for “E-2”)
Note: Counting status is undefned if E-2 is selected on E-1 and if E-1 is selected
on E-2.
When the status is defined as above, both energy counters count while digital input
is not on (=1), but if either one or both digital inputs are on (=1) then counters will
not count.
PUL SE o-1 : If this parameter is selected, in every increase in output 1,
one pulse is counted. Output 1 parameter can be set as :
ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
/ Capacitive),  r-L (Reactive Inductive), r-C (Reactive Capacitive).
PUL SE o-2 : If this parameter is selected, in every increase in output 2,
one pulse is counted. Output 2 parameter can be set as :
ACt (Export/Import),  A-I (Active Import), A-E (Active Export), rEA (Inductive
/ Capacitive),  r-L (Reactive Inductive), r-C (Reactive Capacitive).
By using UP-DOWN buttons, select “on”, “ý-1”, “ý-2” or “E-1 / E-2”.
This menu is used for activating the user password.
After the user password is activated, while the instant values are
observed,user password is required in order to enter to the
menu. If the wrong user password is entered, user can not enter
to the menu.
Note:
  Factory default value of user password is “0000”
+
_
N
L1
L2
L3
1 A
L1
N
Current Measuring Input
Auxiliary
Supply
L1
L2
L3
N
1
2
3
4
5
6
Voltage Measuring Input
k
l
K
L
k
l
K
L
k
l
K
L
I
L1
I
L2
I
L3
RS485
GND
A TR
Max: 30 VDC
Pul 1
Pul 2
Pul C
InC In1 In2
B
( 12-48V DC )
13 14 15 16 17 18
19 20 21 22
7
8
9
10
11
12
3 Phase neutral
+
_
+
_
L1
L2
L3
1 A
L1
N
Current Measuring Input
Auxiliary
Supply
L1
L2
L3
N
1
2
3
4
5
6
Voltage Measuring Input
k
l
K
L
k
l
K
L
I
L1
I
L2
I
L3
RS485
GND
A TR
Max: 30 VDC
Pul 1
Pul 2
Pul C
InC In1 In2
B
( 12-48V DC )
13 14 15 16 17 18
19 20 21 22
7
8
9
10
11
12
3 Phase without neutral current input  with
Aron wiring configuration
+
_
L1
L2
L3
k
l
K
L
k
l
K
L
1 A
L1
N
Current Measuring Input
Auxiliary
Supply
L1
L2
L3
N
1
2
3
4
5
6
Voltage Measuring Input
I
L1
I
L2
I
L3
RS485
GND
A TR
Max: 30 VDC
Pul 1
Pul 2
Pul C
InC In1 In2
B
( 12-48V DC )
13 14 15 16 17 18
19 20 21 22
7
8
9
10
11
12
3 Phase without neutral current input  with
Aron wiring configuration
*Available only for EPR-04S
Note: For CT-25 models:
PR 19 Box Connection Diagram
3 Phase without neutral
L1
L2
L3
1 A
L1
N
k
l
K
L
k
l
K
L
k
l
K
L
Current Measuring Input
Auxiliary
Supply
L1
L2
L3
N
1
2
3
4
5
6
Voltage Measuring Input
I
L1
I
L2
I
L3
RS485
GND
A TR
Max: 30 VDC
Pul 1
Pul 2
Pul C
InC In1 In2
B
( 12-48V DC )
13 14 15 16 17 18
19 20 21 22
7
8
9
10
11
12
k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.