It is essential to set the correct date and the time to obtain the right dates on the datalog menu
Date (DD/MM/YYYY)
4.3  Date and Time
Figure 15: 
Setting the date
Time (Hour / Minute / Seconds)
Figure 16: 
Setting the time
4.4   RS-485 (PC Communication Settings)
All the measured parameters can be transferred to PC through the MPR-SW Software by MODBUS RTU Protocol.
Device can be configured with PC through the MPR-SW Software.
It is necesarry to set the Baud Rate, Address and Parity values to the device correctly.
RS-485 has 3 sub-menus
‘‘Addr: ...’’ ,        ‘‘Bd: ...’’,        ‘‘Prt: ...’’
Addr (Address Information)
Address  Information  can  be  set  between  1  and  247.
Figure 17: 
Setting the address information
Bd (Baud Rate Value)
Baud rate is set between 1200 bps and 38400 bps.
Figure 18: 
Setting the baud rate value
Warning :
You may quit all settings any time by           key.
You must record any change in the settings by         menu key.