Device has 2 relays (NO Normally open) for alarm outputs.
Any 3 parameters can be associated with any of the two relays at the same time. For each parameter, under,
over, hysterisis and time delay values can be programmed. If the measured value of the set parameter exceeds
the programmed values during the delay time, output relay switches on.
4.6    1. Relay 1 and 2. Relay 2
Event
Figure 23: 
Active relays are displayed on LCD.
Relay 2 is
switched on
Relay 1 is
switched on
When “event” is on, the associated parameter array is recorded in case any of the output relays are switched
on / off, regardless of period. So, the parameter values can be examined at the time of relay switching on.
Warning :
You may quit all settings any time by           key.
You must record any change in the settings by         menu key.
Figure 22: 
Setting the event
1. Relay 1 / (2. Relay 2)
The list of the parameters which can be associated with relays are marked
with * on parameter table on page 43.
Relay 1 / (Relay 2) has 16 sub-menus.
Cfg:
 Configiration
Pr :
Parameter
Hi :
High (over)
Lo :
Low (under)
Hs :
Hysterisis
Dly:
Time Delay
Menu of 1st Parameter
“Pr1:...”,  “Hi1:...”, “Lo1:...”, “Hs1:...”, “Dly1:...”
Menu of 2nd Parameter
“Pr2:...”, “Hi2:...”, “Lo2:...”, “Hs2:...”, “Dly2:...”
Menu of 3rd Parameter
“Pr3:...”, “Hi3:...”, “Lo3:...”, “Hs3:...”, “Dly3:...”
By this parameter, relays can be configured as “Alarm Output”
(Cfg: Alarm) or as “Remote Control” (Cfg: DOut).
Cfg (Configuration)
Figure 24: 
Relay control type setting