Curve 3: 
With increasing depth 
ρ
E is not decreasing: a strip conductor electrode is 
advisable. 
As measuring results are often distorted and corrupted, for example, by 
underground pieces of metal and underground aquifers, a second 
measurement, in which the spike axis is turned by an angle of 90 °, is 
always advisable (see graph below). 
 
H
S
E
ES
90°
I
 
edw022.eps 
Measurement of Resistances 
Resistance Measurement (R~)  
This measuring function determines the ohmic resistance between 0.02 
Ω
 and 300 k
Ω
The measurement is done with ac voltage. For measurements of very low resistances a 
compensation of the connecting leads is suggested (see Compensation of Measuring 
Lead Resistance
). 
 
edw023.eps 
Figure 12. Resistance Measurement (R~) 
1.  Turn central rotary switch to position "R~". 
2.  Connect instrument as shown in Figure 12.