Earth/Ground Tester 
 
Operation 
19 
Stakeless Ground Loop Measurement 
With this test method, two clamps are placed around the earth ground rod or the 
connecting cable and each are connected to the Tester. Earth ground stakes are not 
used. A known voltage is induced by one clamp, and the current is measured with the 
second clamp. The tester automatically determines the ground loop resistance at this 
ground rod.  
1. Select 
. See Figure 8. 
2.  Connect current clamps. 
Connect the inducing clamp (see Models and Accessories) to terminals H/C2 and 
E/C1 with the supplied safety test leads (1.5 m) as shown. 
Note 
Use the recommended current clamp for inducing only. 
Other current clamps are not suited. 
Connect the second current clamp using the adapter cable (sensing current 
clamp). 
Clamp both current clamps around the earth electrode, which will subsequently be 
measured. 
Note 
Minimum distance between the two current clamps is 
10 cm.  
3. Push 
START
 indicates that measurement is in progress. For continuous 
measurement, continue to push the START button. 
4.   indicates completed measurement. The result is kept on display until a new 
measurement is started or the rotary switch is turned.