Fluke Fluke 4325170 User Manual

Product codes
4325170
Page of 40
 
Earth/Ground Tester 
 
Advanced Operation 
21 
Advanced Operation 
The Tester uses advanced features to measure earth resistance of a single high voltage 
pylon and soil resistivity for calculation and design of earthing systems. 
Measurements on High Voltage Pylons 
The measurement of the earth resistance of a single high voltage pylon usually requires 
the overhead earth wire to be disengaged (lifted off) or the separation of the earthing 
system from the pylon construction. Otherwise, false reading of the resistance of the 
pylon earth electrode are liable to occur because of the parallel circuit of the other pylons 
connected to each other by an overhead earth wire.  
The new measuring method employed in this instrument - with its external current 
transformer to measure the true current flowing through the earth electrode - allows 
measurements of earth electrode resistances without disconnection of the earthing 
system or disengaging the overhead earth wire. See Figure 9. 
1623-2 EARTH/GROUND TESTER
START
S/P2
H/C2
4 Probe
>20 m
>20 m
1
2
3
4
 
edv016.eps 
Figure 9. Earthing Resistance without Disengaging the Overhead Earth Wire