Fluke Fluke 4325155 User Manual

Product codes
4325155
Page of 40
 
Earth/Ground Tester 
 
Specifications 
31 
Measurement principle: Current and voltage measurement 
Measurement voltage: 
Um = 48 V ac 
Short-circuit current: 
> 50 mA ac 
Meas. frequency: 
128 Hz 
Probe resistance (R
S
): 
max 100 k
Ω
 
Auxiliary earth electrode resistance (R
H
): 
max 100 k
Ω
 
Additional error from R
H
 and R
S
: R
H
[k
Ω
]  R
S
[k
Ω
]/Ra[
Ω
]  0.2 % 
RA 3-Pole and 4-Pole selective ground resistance measurement with current 
clamp 
(RA ) 
Resolution Measurement 
range  Accuracy 
Operating 
error 
0.001 to 10 
Ω
 0.020 
Ω
 to 19.99 k
Ω
 
±
(7% rdg + 3 d) 
±
(10% rdg + 5 d) 
Measurement principle: Current/voltage measurement (with external current clamp) 
Measurement voltage: 
Um = 48 V ac 
Short-circuit current:  
> 50 mA ac 
Measurement frequency: 
128 Hz 
Probe resistance (Rs): 
max 100 k
Ω
 
Auxiliary earth electrode resistance (Rh): 
max 100 k
Ω
 
Stakeless ground loop measurement (
) 
Resolution Measurement 
range 
Accuracy  Operating 
error 
0.001 to 0.1 
Ω
 0.020 
Ω
 to 199.9 
Ω
 
±
(7% rdg + 3 d) 
±
(10% rdg + 5 d) 
Measuring principle: Stakeless measurement of resistance in closed loops using two current 
clamps  
Measurement voltage: 
Um = 48 V ac (primary) 
Measurement frequency: 
128 Hz 
Noise current (I
ext
): max 
I
ext
 = 10 A (ac) (Ra < 20 
Ω
 max 
I
ext
 = 2 A (ac) (Ra > 20 
Ω
The information about stakeless ground loop measurements is only valid when used in 
conjunction with the recommended current clamps at the minimum distance specified.