Ht Instruments COMBI G2VDE-tester 1009990 Data Sheet
Product codes
1009990
COMBIG2
Rel 1.00 of 27/08/14
Professional installation safety tester
Pag 6 of 6
HT ITALIA SRL
Via della Boaria 40 - 48018 Faenza (RA)- Italy
Via della Boaria 40 - 48018 Faenza (RA)- Italy
Tel: +39-0546-621002 - Fax: +39-0546-621144
email: export@htitalia.it - web: http://www.ht-instruments.com
email: export@htitalia.it - web: http://www.ht-instruments.com
2. GENERAL SPECIFICATIONS
DISPLAY AND MEMORY:
Features:
Features:
Touch screen, color graphic LCD, 320x240mm
Memory:
999 locations, 3 marker levels
Communication:
Optical-USB and built-in WiFi
POWER SUPPLY:
Batteries:
Batteries:
6 x 1.2V(rechargeable) type AA or 6 x 1.5V type AA
Battery life:
> 500 test for each funtions
Auto Power OFF:
after 5 min of idleness (disabled)
MECHANICAL FEATURES:
Dimensions (L x W x H):
Dimensions (L x W x H):
225 x 165 x 75mm
Weight (included batteries):
1.2kg
WORKING ENVIRONMENTAL CONDITIONS:
Reference temperature:
Reference temperature:
23°C
5°C
Working temperature:
0°
40°C
Allowed relative humidity:
< 80% HR
Storage temperature:
-10
60°C
Storage humidity:
< 80% HR
TEST VERIFIES REFERENCE STANDARDS:
Continuity test with 200mA:
Continuity test with 200mA:
IEC/EN61557-4
Insulation resistance: IEC/EN61557-2
Fault loop impedance:
Fault loop impedance:
IEC/EN61557-3
RCD test:
IEC/EN61557-6
Phase sequence:
IEC/EN61557-7
Multifunction: IEC/EN61557-10
Prospective short circuit current:
Prospective short circuit current:
EN60909-0
Earth resistance on TN systems:
EN61936-1 + EN50522
GENERAL REFERENCE STANDARDS:
Safety of measuring instruments:
Safety of measuring instruments:
IEC/EN61010-1, IEC/EN61010-031, IEC/EN61010-2-032
Product type standard:
IEC/EN61557-1
Technical documentation :
IEC/EN61187
Insulation: double
insulation
Pollution degree:
2
Encapsulation :
IP40
Overvoltage category:
CAT III 240V
(to ground), max 415V between inputs
Max height of use:
2000m
This instrument complies with the requirements of the European Low Voltage Directives 2006/95/EEC