Fluke 1652C06-TPOLEKITVDE-tester 4425908 User Manual

Product codes
4425908
Page of 66
 Electrical 
Installation 
Tester 
 Specifications 
57 
Operating Ranges and Uncertainties per EN 61557 
Function Display 
Range 
EN 61557 
Measurement 
Range Operating 
Uncertainty 
Nominal Values 

EN 61557-1 
0.0 V ac – 500 V ac 
50 V ac – 500 V ac 
±
(2% + 2 dgt) 
U
N
 = 230/400 V ac 
f = 50/60 Hz 
RLO 
EN 61557-4 
0.00 
Ω
 - 2000 
Ω
 
0.2 
Ω
 - 2000 
Ω
 
±
(10 % + 2 dgt) 
4.0 V dc <U
<24 V dc 
R
LO 
2.00 
Ω
 I
200 mA 
RISO 
EN 61557-2 
0.00 M
Ω
 - 1000 M
Ω
 
1 M
Ω
 - 200 M
Ω
 
±
(10 % + 2 dgt) 
200 M
Ω
 - 1000 M
Ω
 
±
(15 % + 2 dgt) 
U
N
 = 50 / 100 / 250 / 500 
/ 1000 V dc 
I
N
 = 1.0 mA 
Z
I
 (No Trip) 
0.00 
Ω
 - 2000 
Ω
 
0.4 
Ω
 - 2000 
Ω
 
±
(15
 
% + 6 dgt) 
Z
I
 (Hi Current) 
0.00 
Ω
 - 2000 
Ω
 
0.2 
Ω
 - 200 
Ω
 
±
(10 % + 4 dgt) 
Z
I
 (Hi Current, Hi Res)
0 m
Ω
 - 9999 m
Ω
 
100 m
Ω
 - 9999 m
Ω
 
±
(8 % + 20 dgt) 
ZI 
EN 61557-3 
R
E
 
0.00 
Ω
 - 2000 
Ω
 
10 
Ω
 - 1000 
Ω
 
±
(10 % + 2 dgt) 
U
N
 = 230/400 V ac 
f = 50/60 Hz 
I
K
 = 0 A – 10.0 kA 
Δ
0.0 ms – 2000 ms 
25 ms – 2000 ms 
±
(10 % + 1 dgt) 
Δ
T = 10 / 30 / 100 / 300 / 
500 / 1000 / VAR mA 
Δ
T, I
Δ
EN 61557-6 
I
Δ
N
 
3 mA – 550 mA 
(VAR 3 mA – 700 mA)
3 mA – 550 mA 
±
(10 % + 1 dgt) 
I
Δ
N
 = 10 / 30 / 100 / 300 / 
500 / VAR mA 
RE 
EN 61557-5 
0.0 
Ω
 - 2000 
Ω
 
10 
Ω
 - 2000 
Ω
 
±
(10 % + 2 dgt) 
f = 128 Hz 
Phase 
EN 61557-7 
 
1 : 2 : 3