Tele 110200 Time Delay Relay, Timer, 1 CO contact 12 - 240 V DC/AC 110200 Data Sheet

Product codes
110200
Page of 2
Änderungen und Irrtümer vorbehalten
Subject to alterations and errors
www.tele-power-net.com
Types
Functions
Supply voltage
Part Nr. (PQ 1) Part Nr. (PQ 10)
E1ZM10 12-240V AC/DC
E, R, Ws, Wa, Es, Wu, Bp
12-240V AC/DC
110100
110100A
E1ZM10 24-240V AC/DC
E, R, Ws, Wa, Es, Wu, Bp
24-240V AC/DC
110200
110200A
E1ZMQ10 24-240V AC/DC
E, R, Wu, Bp
24-240V AC/DC
110202
110202A
E1Z1E10 24-240V AC/DC
E
24-240V AC/DC
110204A
with control input
without control input
E1ZM, E1Z1
Functions
ON delay (E)
When the supply voltage U is applied, the set interval t begins (green 
LED U/t fl ashes). After the interval t has expired (green LED U/t 
illuminated) the output relay R switches into on-position (yellow LED 
illuminated). This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the expiry of the interval t, 
the interval already expired is erased and is restarted when the supply 
voltage is next applied.
E
LED U/t
R
t
U
<t
OFF delay (R)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated). When the control contact S is closed, the output 
relay R switches into on-position (yellow LED illuminated). If the control 
contact is opened, the set interval t begins (green LED fl ashes). After 
the interval t has expired (green LED U/t illuminated) the output relay 
switches into off-position (yellow LED not illuminated). If the control 
contact is closed again before the interval t has expired, the interval 
already expired is erased and is restarted.
Single shot leading edge with control input (Ws)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated). When the control contact S is closed, the output 
relay R switches into on-position (green LED U/t illuminated) and the 
set interval t begins (green LED U/t fl ashes). After the interval t has 
expired (green LED U/t illuminated) the output relay switches into off-
position (yellow LED not illuminated). During the interval, the control 
contact can be operated any number of times. A further cycle can only 
be started when the cycle run has been completed.
Single shot trailling edge with control input (Wa)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated).
Closing the control contact S has no infl uence on the condition of the 
output R. When the control contact is opened, the output relay switches  
into on-position (yellow LED illuminated) and the set interval t begins 
(green LED U/t fl ashes). After the interval t has expired (green LED U/t 
illuminated), the ouput relay switches into off-position (yellow LED not 
illuminated). During the interval, the control contact can be operated 
any number of times. A further cycle can only be started when the cycle 
run has been completed.
ON delay with control input (Es)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated).
When the control contact S is closed, the set interval t begins (green 
LED U/t fl ashes). After the interval t has expired (green LED U/t 
illuminated) the output relay R switches into on-position (yellow LED 
illuminated). This status remains until the control contact is opened 
again.
If the control contact is opened before the interval t has expired , the 
interval already expired is erased and is restarted with the next cycle.
Single shot leading edge voltage controlled (Wu)
When the supply voltage U is applied, the output relay R switches 
into on-position (yellow LED illuminated) and the set interval t begins 
(green LED U/t fl ashes). After the interval t has expired (green LED U/t 
illuminated) the output relay switches into off-position (yellow LED not 
illuminated). This status remains until the supply voltage is interrupted. 
If the supply voltage is interrupted before the interval t has expired, the 
output relay switches into off-position. The interval already is erased 
and is restarted when the supply voltage is next applied.
Flasher pause fi rst (Bp)
When the supply voltage U is applied, the set interval t begins (green 
LED U/t fl ashes). After the interval t has expired, the output relay R 
switches into on-position (yellow LED illuminated) and the set interval t 
begins again. After the interval t has expired, the output relay switches 
into off-position (yellow LED not illuminated).
The output relay is triggered at a ratio of 1:1 until the supply voltage is 
interrupted.
R
LED U/t
R
S
t
<t
U
t
<t
Ws
LED U/t
R
S
t
U
t
A1 B1
15
A2 16 18
A1
R
15
16 18
~
(+)
(-)
A2
S
A1 B1
15
A2 16 18
A1
R
15
16 18
~
(+)
(-)
A2
Wa
LED U/t
R
S
t
U
t
Es
LED U/t
R
S
t
U
<t
Wu
LED U/t
R
t
U
<t
Bp
LED U/t
R
t
U
t
t
t
Connections
Ordering information