ConiuGo 700100107 EasyGuard II 700100107 User Manual

Product codes
700100107
Page of 54
 
8
 
Revision 9.0 
GSM Alarm & Telemetry systems 
Digital inputs  
The digital inputs are dedicated to simple sensors which support the module with a 
contact indicating a logic level (high “1” or  low “0”). Those sensors activate an inter-
nal switch (e.g. relay contact of a motion tracker) or are a swith itself (door and win-
dow  contacts).  The  digital  inputs  have  to  be  used  by  a  potential  free  contact  to 
“ground". The status of the input then changes from “1" to “0". The contacts of 
the switch resp. the relay will be sourced by the GSM Module input with 5 V, 15 mA. 
The contacts should be able to switch a minimum load of 10 V, 50 mA. 
 
 
The digital inputs are only suitable for potential free contacts. 
You are not allowed to connect them with voltage. 
 
Analog inputs 
The  analog  inputs  are  dedicated  for  meassurements  and  are  10  Bit  inputs.  This 
could be meassurement of different kinds (e.g. temperature, weight, air damp, etc.). 
The modul reacts, depending on the kind of equipment on the sensor, on input cur-
rent  or  input  voltage.  The  incoming  signals  are  converted  by  the  module  into  the 
measures  that correspond  with  the  settings  of the user.  The  signals that  are  meas-
ured  permanently  are  supervised  by  the  module  regarding  to  the  range  that  is  de-
fined by the two valued “Min.” and “Max.”. 
Integrated in the Module is an analog signal conditioning which consist of 4 current 
inputs  of  0/4  -  20  mA  resp.  0  –  15  V  in  the  basic  series.  All  minus  input  poles  are 
connected internal to the “ground” of the module. The input voltage must not exceed 
15 V DC. 
The  analogous  inputs  don't  have  any  potential  separation.  Therefore  it  has  to  be 
taken  care  on  the  correct  grounding  of  all  devices  that  are  connected  to  the  analo-
gous inputs of the module! 
 
If you need analogous inputs that are conditioned to special sensors this should be 
announced  with  your  order.  Any  change  in  the  signal  conditioning  later  has  to  be 
done by the manufacturer and the whole device has to be returned to the producer. 
The will cause costs of 30,- € plus delivery cost,. 
 
 
The inputs must be used strictly within the parameters of the 
technical specification. Do not connect the GSM- module to any 
other device that is capable of dangerous voltage or exceeds 
the maximum input!