4.2  Command Sources (P0700) 
This parameter determines from which source the inverter receives the Start, Stop 
and Reverse commands. The SINAMICS G110 has two default settings depending 
on the inverter variant, see the Quick Commissioning Flowchart on page 48. 
NOTES 
The ramp times and ramp-smoothing functions also affect how the motor starts and 
stops. For details of these functions, please refer to parameters P1120, P1121 and 
P1130 in the Parameter List. 
Starting the motor 
Analog Variant 
 
Default value: 
2 – Terminal 3 (DIN 0, high) 
 
Other settings: 
see P0701 to P0704 in the Parameter List 
 
USS Variant 
 
Default value: 
5 – Terminals 8 and 9 (RS485) 
 
Other settings: 
see P0701 to P0703 in the Parameter List 
Stopping the motor 
There are several ways to stop the motor (for OFF1 – OFF 3 see page 53): 
NOTE 
All OFF commands are active low. 
Analog Variant 
 
Default value: 
2 – Terminal 3 (DIN 0, low) 
♦  OFF1 
2 – Terminal 3 (DIN 0, low) 
♦  OFF2 
Off button on Basic Operator Panel, pressing the Off 
button once long (two seconds) or twice 
♦  OFF3 
no standard setting 
 
Other settings:  
see P0700 to P0704 in the Parameter List 
USS Variant 
 
Default value: 
5 – Terminals 8 and 9 (RS485) 
♦  OFF1 
Control word 1 (r0054), bit 00 
♦  OFF2 
Off button on Basic Operator Panel, pressing the Off 
button once long (two seconds) or twice; control word 1 
(r0054), bit 01 
♦  OFF3 
Control word 2 (r0054), bit 02