04/2003 Troubleshooting 
SINAMICS G110    Operating Instructions 
 
6SL3298-0AA11-0BP0 
57
 
6 Troubleshooting 
WARNINGS 
 
Repairs on equipment may only be carried out by Siemens Service, by repair 
centers authorized by Siemens or by authorized personnel who are 
thoroughly acquainted with all the warnings and operating procedures contained 
in this manual. 
 
Any defective parts or components must be replaced using genuine Siemens 
authorized parts. 
 
Risk of electric shock. The DC link capacitors remain charged for five minutes 
after power has been removed. It is not permissible to open the equipment 
until 5 minutes after the power has been removed.
 
6.1  Troubleshooting with the Standard Inverter LED 
The following is a description of the fault and warning indications given by the LED 
on the Standard Inverter: 
 
Inverter Off/No supply:  
No LED lit. 
 
Power On/Ready:            
1000 ms On/1000 ms Off 
 
Inverter Running OK:      
Steady LED 
 
General Warning:           
500 ms On / 200 ms Off 
 
Fault Condition:              
100 ms On / 100 ms Off 
6.2  Troubleshooting with the BOP 
If the display shows a fault or warning code, please consult the Faults and Warning 
section of the SINAMICS G110 Parameter List. 
If the motor fails to start when the ON command has been given: 
 
Check that P0010 = 0. 
 
Check that a valid ON signal is present (see example on page 58). 
 
Check that  P0700 = 1 (for BOP control) or 
 
P0700 = 2 (for digital input control) or 
 
P0700 = 5 (for USS input control – USS variant only) 
 
P0719 is set to the correct Command and Frequency Setpoint.  
 
Check that the setpoint is present (0 to 10V on Terminal 9) or the setpoint has 
been entered into the correct parameter, depending upon the setpoint source 
(P1000). See the Parameter List for further details. 
If the motor fails to run after changing the parameters then: 
1.  Set P0010 = 30 
2.  Set P0970 = 1 
3. Press   to reset the inverter to the factory default parameter values. 
4.  Use a switch between terminals 3 and 6 on the control board. 
5.  The inverter should now run to the setpoint defined by either the analogue 
input or transmitted via the USS serial link communications. 
NOTE 
Motor data must relate to the inverter data power range and voltage.