Novatek SINGLE-PHASE VOLTAGE RELAY RN-113 RN-113 Data Sheet

Product codes
RN-113
Page of 5
1.APPLICATION
Voltage monitoring relay RN-113 (hereinafter  RN-113) is designed to turn  OFF home used consumer equipment or
industrial power load in case of unallowable voltage drops or fluctuations. And when the voltage parameters returns back
to normal values after the fault – it automatically turns ON the power load with the user adjusted time delay (autoreclosing
time).
If power load is less than 7,0 kW (32A) then RN-113 may operate with the power load directly using its own output
terminals;
If power load is more than 7,0 kW (32A) then it should be commutated using contactor of appropriate power rating. So
RN-113 operates with the magnetic coil of the contactor and thus turn ON/OFF the power load when necessary. Kindly
note that contactors of appropriate power rating should be chosen by User and not supplied along with RN-113.
RN-113  has four independent modes of operation:
1.
Minimal/Maximal voltage protection relay;
2.
Minimal voltage protection relay;
3.
Maximal voltage protection relay;
4.
Turn ON time delay relay.
Digital display of RN-113 indicates the value of acting voltage level and the remaining time to Open/Close
(ON/OFF) state of the output contacts. The position of the contacts is additionally shown using green color LED 
indicator.
 
1-4 - input terminals 
5-7- output terminals 
8- ON/OFF state indicator showing the position of the output contacts (power load)
9- toggle switch (ON/OFF): Maximal voltage tripping (U
max
)
10- toggle switch (ON/OFF): Minimal voltage tripping(U
min
)
11- Digital LED segment display
12- Autoreclosing time delay (T
on
)
13- Minimal voltage tripping threshold  (U
min)
14- Maximal voltage tripping threshold (U
max)
Figure 1
 –  Front panel controls and dimensions diagram
2. TECHNICAL CHARACTERISTICS 
RN-113 
                                                                                                                            
NOVATEK-ELECTRO