Novatek CONTROL UNIT REFRIGERATING MSK-102-1 MSK-102-1 Data Sheet

Product codes
MSK-102-1
Page of 7
- 5 - 
NOVATEK-ELECTRO
       
                                                                                                                                                             
MCK-102-14 
                          
 
 
In thermostat mode MCK-102-14  permanently controls so that the temperature inside refrigeration 
chamber will not go out the preset limits (parameters LAL and HAL). These parameters are not under control 
during defrost mode and in case of voltage interruptions. 
To disable premature alarm signalization about temperature alarm situations the following parameters are 
used: 
,  and .  
If voltage monitoring mode is enabled (parameter 
=1) – then MCK-102-14 performs permanent control 
over the voltage parameters in all modes of operation. If unallowable voltage levels are detected MCK-102-11 
turns the compressor OFF.  
In case of removal emergency situation on voltage the MCK-102-14 begins processing of program from 
start. 
All alarm situation codes are shown in table 1 below: 
 
Fault signals on the indicator 
Alarm signals on the indicator 
t tttt tt tttttttttt 
Er1 
t ttt ttt tttttttt 
 
t ttttttttttt ttttttttttttt tttt ttt tttttt 
Er2 
ttt  ttt tttttttt 
 
t tttt-ttttttttt ttttttttttttt tttt ttt tttttt 
Er3 
Minimal voltage 
 
 
 
Maximal voltage 
 
 
 
8 PROGRAMMABLE PARAMETERS AND ADJUSTABLE FUNCTIONS 
 
Table 2 
 
Parameters and 
functions  
Display 
indication 
Min. 
value 
Max. 
value 
Default 
settings  
Actions  
Temperature operation 
setting point, 
°
С 

-45 
50 
Temperature value should be adjusted 
by user as per requirement 
Thermostat mode 
In thermostat mode compressor turns ON when the temperature reaches the value of 
SP+diF. Compressor turns OFF when the temperature reaches the value of SP 
Differential, 
°
С 

20 
The difference value between Setting 
Point (SP) temperature and the 
temperature when the compressor 
should turn ON 
Temperature sensor 
calibration, 
°
С 

-9,9 
9,9 
Scale offset to the value of CA1 in 
reference to the value measured by 
temperature sensor 
Temperature 
indication 

0-value indication without decimal 
units 
1-value indication with decimals 
Signalization 
 
The way to set alarm 
temperature: 
0 – absolute value  
1 – relative value 
basing the set point 

Interpretation of the HAL and LAL 
parameters 
Alarm indication turns ON 
depending the mode values:
 
0 – when the temperature value 
reaches HAL or LAL thresholds 
1 – when upper temperature reaches 
+ or lower temperature 
reach 
- 
Deviation of positive 
temperature  

Att=0 
Att=1 
 
LAL 
+1 
 
50 
50 
 
 
10 
 
Deviation of negative 
temperature  

Att=0 
Att=1 
 
-45 
 
HAL-1 
50 
 
  
10