Novatek CONTROL UNIT REFRIGERATING MSK-102-1 MSK-102-1 Data Sheet

Product codes
MSK-102-1
Page of 7
- 6 - 
MCK-102-14   
                                                                                                                                                                
NOVATEK-ELECTRO
 
Parameters and 
functions  
Display 
indication 
Min. 
value 
Max. 
value 
Default 
settings  
Actions  
Time delay in case of 
temperature alarm 
situation, min 

90 
30 
 
Time delay for the 
temperature alarm 
after turning ON, hours 

48 
 
Time delay for the 
temperature alarm 
after defrost, hour 

10 
 
Compressor 
 
Minimal operation time 
for the compressor, 
min 

15 
Protection against frequent turns ON 
Minimal pause bet-
ween consequential 
turns ON of 
compressor, min 

15 
Protection against frequent turns ON 
Compressor turn ON 
time in case of the 
temperature sensor 
fault, min 

120 
10 
 
Duration of the OFF 
state of the 
compressor in case of 
the temperature 
sensor fault, min 

120 
10 
 
Compressor protection 
from temperature 
sensor fault 

0 – compressor permanently OFF 
1 – compressor permanently ON 
2 – operation using COn and COF 
parameters 
Defrost 
 
Time interval between 
defrosts, hours 

48 
 
Method of the Timing 
countdown between 
defrosts 
 

1- DG-Frost method when the defrost 
starts (dit) depending the total 
operating time of the compressor  
0 – basing the real time – the fre-
quency of defrosts depend basing the 
real time. Thus time interval between 2 
defrosts will be the same 
2- compressor shut down; defrost 
starts every time when compressor 
turns OFF 
Maximal duration of 
the defrost, min 

180 
30 
 
Display indication 
during defrost 

0 – actual temperature 
1 – temperature at the beginning of 
the defrost 
2 – value of Setting point (SP
3 – indication “
”  
Start of the defrost 
after turning ON 

0 – No    
1 – Yes