Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 Data Sheet

Product codes
OM-310
Page of 28
- 18 - 
ОМ-310
                                                                                                                                                       
NOVATEK-ELECTRO
 
 
 
Figure  2.2 -  
ОМ-310 connection to PC schematic 
 
2.4.4.3. Communication protocol 
The exchange between PC and 
ОМ-310 is effected via data packages. Data packet format is given in Table 2.1. 
 
Table 2.1 
 
START 
 silence interval – over 2msec at 9600 baud transfer rate, or over 4 msec at 19200 baud 
transfer rate  
ADR 
 
ОМ-310 communication address (8 bit) 
CMD 
 Command code 8 bit 
DATA 0 
 Data contents: 
N*8 data bit (n<=24) 
…. 
DATA (n-1) 
CRC CHK low 
 CRC checksum 
 16 bit 
CRC CHK high 
END 
silence interval –  over 2msec at 9600 baud transfer rate, or over 4 msec at 19200 baud 
transfer rate 
  
2.4.4.4 CMD (command code) and DATA (data symbols)  
Data symbols format depends on command codes.  
Command code –0x03, n-words read. 
For example, read 2 continuous words swapped from 210
2H in ОМ-310  initial address with 01H communication 
address (Table 2.2) 
 
Table 2.2 
 
Command message 
Response message 
ADR 
 0x01 
ADR 
 0x01 
CMD 
 0x03 
CMD 
 0x03 
Start data address 
 0x21 
 0x02 
Data amount, bytes 
 0x04 
Data amount in words 
 0x00 
 0x02 
Data contents by address 
0x17 
0x70 
CRC CHK low 
 0x6F 
Data contents by address 
0x00 
0x00 
CRC CHK high 
 0xF7 
CRC CHK low 
0xFE 
 
 
CRC CHK high 
0x5C 
 
Command code 0x06, record – one word 
Using this command is not recommended as recording incorrest data may lead to 
ОМ-310 failure. 
Data recording is possible only to the programmable parameters addresses (Table 1.5), except for parameters 
listed in Table 2.3.