Phoenix Contact 2810625 MCR-SL-S-1/5-I-DCI-230 Current Measuring Transducer For Sinusoidal AC Currents Up To 5 A 2810625 Data Sheet

Product codes
2810625
Page of 5
Nov 14, 2013    1 / 5
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be
configured using a DIP switch with an operating mode indication through an LED
Product Description
The MACX MCR-SL-CAC-5-I(-UP) current measuring transducers convert sinusoidal alternating currents of 1 A or 5 A into standard
analog signals 0...20 mA or 4...20 mA. The DIP switches, which can be accessed on the upper side of the housing, can be used to
configure the input and output current.The MACX MCR-SL-CAC-5-I current transducer contains a supply voltage range of 19.2 V DC to
30 V DC.The MACX MCR-SL-CAC-5-I current transducer contains a long range version with a supply voltage range of 19.2 V AC/DC to
253 V AC/DC.  
Product Features
 Input/output can be configured via DIP switches
   
  
Key commercial data
package_quantity
1
GTIN
4046356153782
Technical data
Dimensions
Width
22.5 mm
Height
104 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C (-4°F ... 149°F)
Ambient temperature (storage/transport)
-40 °C ... 85 °C (-40°F...185°F)
Maximum altitude
2000 m
Degree of protection
IP20
Input data
Configurable/programmable
Via DIP switches
Operate threshold
0.3 % (1 A)
Operate threshold
0.45 % (5 A)
Setting range for min. input current
0 A AC ... 1 A AC (configurable)