Phoenix Contact 2810625 MCR-SL-S-1/5-I-DCI-230 Current Measuring Transducer For Sinusoidal AC Currents Up To 5 A 2810625 Data Sheet

Product codes
2810625
Page of 5
Nov 14, 2013    2 / 5
Technical data
Input data
Setting range for max. input current
0 A AC ... 5 A AC (configurable)
Overload capacity
2 x I
N (
continuous)
Surge strength
20 x I
N
 (1 s)
Nominal frequency f
N
50 Hz
Frequency measuring range
45 Hz ... 65 Hz
Connection method
Screw terminal block
Output data
Output name
Current output
Configurable/programmable
Via DIP switches
Current output signal
0 mA ... 20 mA (configurable)
Current output signal
4 mA ... 20 mA (configurable)
Max. output current
25 mA
Load/output load current output
< 500 Ω (at 20 mA)
Status display
LED red (error), LED green (ready)
Switching output
Output name
No switching output
Power supply
Supply voltage range
19.2 V AC/DC ... 253 V AC/DC
Max. current consumption
< 30 mA (at U
B
=24 V DC, I
OUT
=20 mA)
Max. current consumption
< 13 mA (at U
B
=230 V AC, I
OUT
=20 mA)
Power consumption
< 0.9 W (at U
B
=24 V DC, I
OUT
=20 mA)
Power consumption
< 3.4 W (at U
B
= 230 V AC, I
OUT
=20 mA)
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
Maximum transmission error
≤ 0.5 % (of nominal range value under nominal conditions)
Maximum temperature coefficient
< 0.02 %/K
Temperature coefficient, typical
< 0.015 %/K
Step response (10-90%)
max. 300 ms
Step response (10-90%)
typ. 200 ms
Surge voltage category
III